Command Syntax
Siemens Building Technologies, Inc. 3-39
EMAUTO (Emergency, Auto status)
Unitary pre-APOGEE APOGEE BACnet
Syntax
EMAUTO(pt1,...,pt16)
pt1
through
pt16
Point name to be set to AUTO status with emergency priority.
This parameter can be a LOOAL or LOOAP point.
Use
Changes the operational status of an ON/OFF/AUTO point to AUTO
(local control) with emergency priority.
A maximum of 16 points can be changed with one EMAUTO
command.
See also
EMFAST, EMOFF, EMON, EMSET, EMSLOW
APOGEE PPCL User’s Manual
3-40 Siemens Building Technologies, Inc.
EMFAST (Emergency, Fast status)
Unitary pre-APOGEE APOGEE BACnet
Syntax
EMFAST(pt1,...,pt16)
pt1
through
pt16
Point name to be set to FAST status with emergency priority.
This parameter can be a LFSSL or LFSSP point.
Use
Changes the operational status of a FAST/SLOW/ STOP point to
FAST with emergency priority.
A maximum of 16 points can be changed with one EMFAST
command.
See also
EMAUTO, EMOFF, EMON, EMSET, EMSLOW