20
2.3 Operational precautions
Figure 13: Measures to limit “stress escalation” in the event of fire
a) Design measures
Implementation of the Silent Extinguishing measures, including the use of an appropriate extin-
guishing agent, CDT systems, Silent Nozzles, a 120-second discharge time and optimal nozzle
placement.
b) Operational management system
A Data Center Integrated Management System to present and prioritize all decision-relevant data,
alarm handling and measure plans for all IT- and technical building management systems.
Normal operation
Selection and qualification of the hard disk drives used in accordance with a predefined checklist
for example, new generations of hard disk drives/technologies will be qualified in terms of their
noise sensitivity.
Pre-alarm
Determine the reason for the pre-alarm as quickly as possible in order to lay the foundation for
subsequent decisions. If possible, prevent escalation to a fire alarm.
1st fire alarm
When the fire alarm is triggered, the event escalates massively. The fire alarm is transmitted to the
fire brigade which appears within minutes.
This is the ideal time to change over from main- to backup data center operation.