User Manual

4/6
Siemens Building Technologies Pressure sensors QBE620-P CA1N1904E
HVAC Products 10.06.2005
Technische Daten
Electrical interface Power supply
Supply voltage
– Max. voltage tolerance
Current consumption
With extra-low voltage only (SELV, PELV)
AC 24 V, 50...60 Hz or DC 18...33 V
±15 % at AC 24 V
< 5 mA
Output signal DC 0...10 V, R
Load >10 k (no electrical isola-
tion, three-wire connection, short-circuit proof
and protected against polarity reversal)
Funktional data Application range 0...40 bar (see "Type summary")
Accuracy:
Total of linearity, hysteresis
and reproducibility
Zero point offset voltage
(FS = Full Scale)
< ± 0.5 % FS
< 50 mV
Temperature drift:
TC zero point
TC sensitivity
< ± 0.05 % FS / K
< ± 0.015 % FS / K
Response time 90 % < 5 ms
Nominal pressure Relative pressure as in "Type summary"
(Measurement of difference from ambient
pressure)
Max. admissible pressure 2 x scale end value of measuring range (FS)
Rupture pressure 3 x scale end value of measuring range (FS)
Media
Admissible temp. of medium
Neutral and mildly corrosive liquids and gases
–15 ... + 80 °C
Maintenance No maintenance required
Orientation Any
Protection Protection standard IP 65 to EN 60 529
Connections Connection cable PVC, lenght 2 m, 3 x 0.25 mm
2
stranded wires
Screwed fitting external thread G1/2"
Environmental conditions Operation to
Climatic conditions
Temperature
Humidity
15...+ 85 °C
<95 % r.h.
Storage/transport
Climatic conditions
Temperature
Humidity
25...+ 70 °C
<95 % r.h.
Standards
Electromagnetic compatibility
Immunity to
Emissions to
EN 61 000-6-2, EN 61 326-1
EN 61 000-6-3, EN 55 022, EN 61 326-1
conformity to EMC directive 89/336/EEC
Materials Base
stainless steel (1.4305)
Measuring element
ceramics diaphragm
Cover Aluminium (Al Mg Si1), with silver-grey pow-
der coating
Sealant FPM rubber
Sealing compound Synthetic resin
Fixing bracket AQB22.1 die-cast aluminium
Mounting kitt AQB51.1 see "Accessories"
Dimensions (Weight) Weight (including packaging) 0.31 kg
.