s Infrastructure & Cities Symaro™ Flush-mount room sensors KNX S-Mode / KNX LTE-Mode / KNX PL-Link AQR253… AQR257… Technical principles CE1P1411en 2013-04-17 Building Technologies
Siemens Switzerland Ltd. Sector Infrastructure & Cities Building Technologies Division Gubelstrasse 22 6301 Zug Switzerland Tel. +41 41-724 24 24 www.siemens.com/sbt © 2013 Siemens Switzerland Ltd. Subject to change 2 / 44 Siemens Building Technologies Flush-mount room sensors AQR253... AQR257...
Contents 1 About this document ..............................................................................5 1.1 Revision history.........................................................................................5 1.2 1.2.1 1.2.2 1.2.3 1.2.4 Before you start.........................................................................................5 Trademarks ...............................................................................................5 Copyright.................................
6.3.3 6.3.4 6.3.5 6.3.6 Room air quality sensor & controller .......................................................26 Universal temperature sensor .................................................................27 Binary inputs............................................................................................27 Fault information .....................................................................................28 6.4 6.4.1 6.4.2 6.4.3 6.4.4 6.4.5 6.4.6 6.4.7 6.4.8 6.4.
Version Date 1 About this document 1.1 Revision history Changes Section 1.2 Before you start 1.2.1 Trademarks Pages The trademarks used in this document and their lawful owners are listed in the table below.. The use of trademarks is subject to international and domestic provisions of the law. Trademark(s) Legal owner KNX® KNX Association, B - 1831 Brussels-Diegem Belgium http://www.knx.
For more details on the products and applications, please refer to: • On the internet: "Technical product data and descriptions" at www.siemens.com/gamma-td • On the intranet (for Siemens employees only) at http://step.bt.siemens.com/portal/index.html • At your next Siemens branch office www.siemens.com/sbt or at your system suppliers. • From the support team in the headquarters fieldsupportzug.ch.sbt@siemens.com if no local POC is available.
2 Device 2.1 Type summary Product number Base + Front module module Measured variables Inputs CO2 Relative Temperature Air quality Passive temp.
2.3 Variant and device parts The room sensor comprises: • One base module with snapped-on mounting plate. • One design frame (ordered as separate accessory) and • One front module. The sensing elements are located in either the base or the front module (see "Type summary"). Base module D B 1411J05 A Front module Frame C A B C D KNX bus connection terminals Mounting plate Anti-theft device Design frame 2.
Connection terminals KNX bus connection Sensor input (NTC 10k) Common sensor ground Binary inputs (NO / NC) 2.4.1 Adhesive address labels The devices are supplied with peel-off adhesive address labels containing the unique KNX ID as alphanumeric and barcode display. AQR2570NF KNX ID Simplifying engineering and commissioning 00FD00086255 Hex The address label can peeled off the device during mounting and stuck to a floor plan or similar.
2.5 Dimensions Base module 12.5 38 50.5 55 70.8 70.8 1410M01 47 55 13.5 Front and base module (assembled without design frame) 10 / 44 Siemens Building Technologies Flush-mount room sensors AQR253... AQR257...
Mounting plate and design frame Mounting plate "CEE/VDE" (square): DELTA line design frame: Mounting plate "British standard" (square): 83 68 30 DELTA miro1 design frame: 11 1410M03 48.5 68 83 3 1 Mounting plate "3 Modular" (horizontal): DELTA azio design frame: Mounting plate "UL" (vertical): Dimensions as for mounting plate "3 Modular" (see above) but vertical. DELTA azio design frame: Dimensions as for DELTA azio design frame (see above), but vertical.
2.6 Environmental compatibility, disposal General notes This device was developed and manufactured with environmentally compatible materials and procedures complying with all relevant environmental standards. Note the following to dispose of the product following its useful life or in case of replacement: • Do not dispose of the device as part of standard household garbage, but as special waste from plastic and steel, ferrite-magnet components. This applies in particular to the PCB.
Please comply with these notes General regulations 3 Safety and EMC optimization 3.1 Notes on safety This section explains general and system-specific regulations for mains and operating voltages. It includes important information for your safety and the safety of the entire plant. Please comply with the following general regulations during engineering and execution: • • • • • Electrical and mains power ordinances for the given country. Other applicable, national regulations.
3.3 Notes on EMC optimization Setting up cable ducts When setting up cable ducts, separate strongly interfering cables from susceptible entities. Cable types • Interfering cables: Motor cables especially from motors supplied by inverters, energy-supplying cables. • Susceptible entities: Control cables, low voltage cables, interface cables, LAN cables, digital and analog signal cables. Separate cables • Both types of cables may be in the same cable duct, but in separate compartments.
4 Mounting and electrical installation 4.1 Mounting Comply with the following notes as well as the mounting instructions [2] to mount the room sensor. Ambient conditions Note the permissible ambient temperature and humidity. See data sheet [1] for environmental conditions. Mounting location Sensor mounted on interior wall of room to be conditioned: • • • • • • • At ca. 1.5 m height in the room and at least 50 cm from the next wall. Not on outside walls. Not in niches or behind curtains.
Connection diagram Maximum line length for universal temperature sensors and binary inputs: 10 m Seal the end of the installation conduit to prevent false measurements due to air drafts. Comply with the various regulations on separating various voltage levels when mounting the temperature sensor (with safety extra-low voltage protection) alongside the recessed conduit boxes connected to the low-voltage power.
Prerequisites 5 Functionality / Use 5.1 Basics 5.1.1 System environment For engineering and commissioning, sound knowledge of KNX networks as well as sufficient knowledge of working with ETS, ACS790, or ABT depending on system environment is a prerequisite. System environments and associated tools: System/Network environment Engineering and commissioning tool(s) KNX PL-Link ABT, SSA KNX LTE-Mode Synco ACS790 KNX S-Mode ETS • For ACS: An interface converter, e.g.
5.3 Functions The room sensor allows for measuring the room temperature, relative humidity, and CO2 concentration in the room. An additional, passive temperature sensor can be connected to measure another temperature. The binary inputs of the room sensor detect the status of up to two connectable, potential-free contacts. As a result, up to four measured values and two states can be transmitted to other members of the building automation and control system via KNX bus.
The integrated room humidity controller and room air quality controller can be used for ventilation control. Both controllers receive up to three switching point values, one blocking/release object, or a switching signal (e.g. motion detector) via the bus. When the respective switching point is exceeded, up to three control signals and one quasi-continuous signal to control the ventilation actuators are transmitted to other bus members. In addition, a signal with the max.
5.4 Application examples Below are a few typical application examples for the AQR257… or AQR253…. room sensors. 5.4.1 Room temperature control This application is recommended primarily for small offices or rooms. Required devices (1) Room temperature sensor comprising basic module AQR257… + front module: AQR2532NNWQ with LED to indicate air quality (2 binary inputs for window contacts on basic module). (2) Window contact S290.
5.4.2 Room temperature control with demand-controlled ventilation This application is suited especially for large rooms with several radiators such as large offices, auditoria, or conference rooms. Required devices (1) Temperature sensor AQR2500… (mounting plate) + AQR2531FNW (NTC 10k). (2) Dual switch 5TD2 111. (3) Room sensor AQR2576… + AQR2535NNWQ (2 binary inputs and 1 analog input NTC 10k on base module). (4) Touch panel UP588/13.
5.4.3 (1) Room sensor AQR2576… + AQR2535NNWQ. (2) Window contact S290. (3) Synco 700 controller RMU730B. (2) 1411B03 Required devices Room temperature, humidity, and air quality control (KNX LTE-Mode, Synco 700) (2) (1) (3) KNX Function description The flush-mounted sensor (1) measures the CO2 concentration, room humidity, and room temperature, and passes on these values to the controller via the KNX bus.
5.4.3.2 Additional application examples for Synco 700 The HVAC Integrated Tool (HIT) contains additional application examples for use with RDG400KN or RDF341 room thermostats under: www.siemens.com/hit In the HIT Start Center, select your country/language Applications Individual rooms Controller range: RDG/RDF from the dropdown list box, and then select operating voltage = AC 24 V. The application examples for the selected range will be displayed.
6 GAMMA building management systems 6.1 Engineering KNX product data The product data (*.vd5 or *.knxprod) must be downloaded from the website and imported in the ETS device catalog for KNX S-Mode engineering. The product data is available at www.siemens.com/hvac-td or www.siemens.com/symaro ETS version If ETS3 is used, make sure to install first ETS3 patch (additional software column SW) for ETS3.0f www.siemens.com/hvac-td For ETS4, make sure the latest version is installed or at least version 4.
6.3.1 Room temperature sensor & controller Base module AQR2570 / AQR2576, with front module AQR2532 / AQR2535 Object index 1 62 5 6 7 8 9 10 11 12 Name in ETS I/O 1 Data point type KNX Value range ID Format Unit Room temperature [°C] O 9.001 2 bytes °C -10.00...+60.00 Fault - room temperature sensor O 1.001 1 bit --0 = Normal / 1 = Faulty If the room temperature sensor is not available or the room temp. cannot be measured, "1 = Faulty“ is generated. Room temperature controller operating I 20.
Object index 19 20 21 22 23 Name in ETS I/O 1 Data point type KNX Value range ID Format Unit Override room r.h. controller I 1.003 1 bit --0 = Normal / 1 = Overridden When overriding a controller, the stage defined as "Stage if overridden" is activated. In this case, only the corresponding object assumes value "1 = On" among objects 20, 21, 22; the two other objects assume value "0 = Off". The continuous control value (obj. 23) issues the parameterized value for the related stage.
Data point type KNX ID Format Control value CO2 stage 1 - on/off O 1.001 1 bit Control value CO2 stage 2 - on/off O 1.001 1 bit Control value CO2 stage 3 - on/off O 1.001 1 bit If the CO2 concentration exceeds a switching point CO2, the control value CO2 for the related stage is switched on. The control value CO2 is again switched off, if the CO2 concentration returns to < switching point CO2 – hysteresis. 35 Control value CO2 – cont.
Object Index D 45 1 Name in ETS I/O Input 1 – up/down Input 1/2 – up/down Input 1 block Input 1/2 block State contact 2 Input 2 - switch Input 2 – send value F Input 2 – switch 2 Input 2 – send value 2 I, O I, O G Input 2 - switch Input 2 - dim H Input 2 – stopstep Input 2 – up/down Input 2 block 46 E 47 F 48 F 49 50 F 51 52 G 53 54 H 55 56 A, B, C, D, E, F, G, H) Value range I, O Data point type KNX ID Format Unit 1.008 1 bit --- I 1.
6.4 Parameter description Factory settings are boldfaced. 6.4.1 Basic configuration Designation Values Description Base module AQR2570 AQR2576 (CO2) Available base module Front module AQR2530 (empty) AQR2532 (T) AQR2533 (rH) AQR2535 (T+rH) A AQR2535...Q (T+rH+LED) Front module configured Activate universal temperature sensor Yes object No A Activation of object for external temperature input NTC 10k.
6.4.3 Universal temperature sensor Base module AQR2570 / AQR2576 Designation Values Description Sensor correction -5...+5K in 0.1K steps 0K Correction of universal temperature sensor value Send after change of 0.2K 0.3K 0.5K 1K 1.5K 2K 2.5K Min. change of universal temperature until a telegram is sent. Send cyclically after 1 min 2 min 3 min 4 min 5 min 10 min 15 min 20 min 30 min 45 min 60 min Time period after which the universal temperature sensor value is resent. 6.4.
6.4.5 Room humidity sensor Base module AQR2570 / AQR2576, with front module AQR2533 / AQR2535 Designation Values Description Send after change of 2% r.h. 3% r.h. 4% r.h. 5% r.h. 7% r.h. 10% r.h. Min. change of room humidity until a telegram is sent. Send cyclically after 1 min 2 min 3 min 4 min 5 min 10 min 15 min 20 min 30 min 45 min 60 min Time period after which the room humidity value is resent. 6.4.
6.4.7 Room air quality sensor Base module AQR2576 Designation Values Description Altitude above sea level [m] 0…3000 m 0m Entry of altitude above sea level at measuring location to correct CO2 measured value Send after change of 50 ppm 100 ppm 150 ppm 200 ppm 250 ppm 300 ppm 400 ppm 500 ppm Min. change of CO2 value until a telegram is sent. Send cyclically after 1 min 2 min 3 min 4 min 5 min 10 min 15 min 20 min 30 min 45 min 60 min Time period after which the CO2 value is resent. 6.4.
6.4.9 Binary inputs Base module AQR2570 / AQR2576 6.4.9.1 General settings Designation Values Description Assignment of inputs Individual Combined Use of binary inputs individually or combined. Input 1/2 --2-button switching 2-button dimming 2-button blinds Function of dual buttons on binary inputs 1 and 2 at combined function for both inputs. Activate blocking object for inputs 1/2 Yes No If the input is blocked (blocking object = 1), state changes for this input no longer are evaluated.
6.4.9.3 Input, 1-button functions When assigning individual functions per input, the same setting options are available for both binary inputs independent of each other. Designation Values Description Type of contact Normally open Normally closed Contact status. Long keypress 0.5 sec 0.6 sec 0.8 sec 1.0 sec 1.2 sec 1.5 sec 2.0 sec 2.5 sec 3.0 sec 4.0 sec 5.0 sec 6.0 sec 7.0 sec Definition of the duration of a keypress, to differentiate between short and long keypress. 6.4.9.3.
6.4.9.3.4 Contact Designation Values Description Type of contact Normally open Normally closed Contact status. Send cyclically after Do not send cyclically 1 min 2 min 3 min 4 min 5 min 10 min 15 min 20 min 30 min 45 min 60 min Time period after which the state at the binary input is resent. Response after bus power recovery Never send * Always send Send if changed* Determines if a measured value at the binary input is sent following bus power restoration.
7 Synco building automation and control system 7.1 Engineering Tool ACS790 is used for engineering in KNX LTE–Mode with devices from the Synco 700 range. This tool is documented in Service- and Operating software ACS790 [5]. ACS790 version For ACS790, version 8.23 must be installed at a minimum.
Variant 2 1. Set addressing mode for the room sensor (briefly press button on device LED is red). 2. In the ACS790 device list, use "Addressing mode…" to select the currently active device Enter a physical address in the "Address assignment" dialog Click "Write". Enter a physical address and short description for the selected room sensor. Close the "Address assignment“ dialog by clicking "Write…“. Repeat these steps for all room sensors to be commissioned.
7.3.3 Room temperature sensors Base module AQR2570 / AQR2576, with front module AQR2532 / AQR2535 Designation Values Description LTE transmission zone ---, 1…4095 Sending zone for KNX LTE-Mode Sensor correction -5...+5K at 0.1K steps 0K Correction of room temperature sensor value Mixing portion universal temperature sensor 0% ext, 100% Int / … / 100% ext 0% Int at 10% steps 0% Ext, 100% Int Mixing of (ext) universal temperature sensor with internal room temperature sensor value.
8 Desigo building automation and control system 8.1 Engineering Engineering at the system level is based on the Automation Building Tool ABT. The web server-based tool SSA (Setup & Service Assistant) allows for data point testing during commissioning. Plug&play commissioning If engineered accordingly, Desigo KNX PL-Link systems can be commissioned using plug&play, i.e. after applying power, commissioning is largely automatic. To this end, the workflow below must be adhered to.
LED status indication KNX PL-Link commissioning LED indication Meaning Dark 1x orange flash Permanent orange flash a) Device is not connected to power. b) Device is powered and works as intended. Feedback on pressing button medium-long. Wait (connection test or reset to factory settings). Flashing red Connection test failed. Red Device is in programming mode. Green Connection test successful. Several room sensors can be connected concurrently or in sequence to power.
8.3.3 Communication Base module AQR2570 / AQR2576, LTE zone per function valid for assigned types. Designation Values Description Geographical zone (apartment) ---, 1...126 Geographical communications address for KNX LTEMode, apartment Geographical zone (room) ---, 1…63 Geographical communications address for KNX LTEMode, room Geographical zone (subzone) ---, 1…15 Geographical communications address for KNX LTEMode, subzone 8.3.
8.3.7 Room air quality sensor RAQS Base module AQR2576 Designation Values Description Altitude above sea level [m] 0…3000 m 0m Entry of altitude above sea level at measuring location to correct CO2 measured value Change of value, COV 50…500 ppm 100 ppm Min. change of CO2 value until a telegram is sent. Heartbeat 120…900s Time period after which the CO2 value is resent. Minimal repetition time 10…60s Minimal delay between consecutive telegrams. 8.3.
8.3.8.2.1 1-button switching LSSB Designation Values Description Action at rising edge --On Off Toggle Reaction after detection of rising edge. Action at falling edge --On Off Toggle Reaction after detection of falling edge. 8.3.8.2.
Siemens Switzerland Ltd. Sector Infrastructure & Cities Building Technologies Division Gubelstrasse 22 6301 Zug Switzerland Tel. +41 41-724 24 24 www.siemens.com/sbt © 2013 Siemens Switzerland Ltd. Subject to change 44 / 44 Siemens Building Technologies Flush-mount room sensors AQR253... AQR257...