Basic Documentation

15 / 44
Siemens Flush-mount room sensors AQR253... AQR257... CE1P1411en
Building Technologies Mounting and electrical installation 2013-04-17
4 Mounting and electrical installation
4.1 Mounting
Comply with the following notes as well as the mounting instructions [2] to mount
the room sensor.
Note the permissible ambient temperature and humidity. See data sheet [1] for
environ
ment
al conditions.
Sensor mounted on interior wall of room to be conditioned:
At ca. 1.5 m height in the room and at least 50 cm from the next wall.
Not on outside walls.
Not in niches or behind curtains.
Not above or near heat sources or shelves.
Not on walls covering heat sources such as a chimney.
Not in the radiation range of heat sources and lighting bodies e.g. spotlights.
Not in areas exposed to direct solar radiation.
4.2 Electrical installation/cabling
The device is designed for flush-mounted cabling.
Run the cables from the wall outlet to the room sensor base module.
Use only suitable cables for the KNX bus.
Do not swap the wires for the KNX cable.
– Red terminal is for CE +
– Gray terminal is for CE –
Comply with local installation regulations.
Use a flat plug to connect the ground cable in the box (in case of switch or mains
plug in the same box).
STOP
Caution
The device is not protected against inadvertent connection to AC 230 V.
Ambient conditions
Mounting location