Basic Documentation

36 / 44
Siemens Flush-mount room sensors AQR253... AQR257... CE1P1411en
Building Technologies Synco building automation and control system 2013-04-17
7 Synco building automation and
control system
7.1 Engineering
Tool ACS790 is used for engineering in KNX LTE–Mode with devices from the Synco
700 range. This tool is documented in Service- and Operating software ACS790 [5].
For ACS
790, version 8.23 must be installed at a minimum.
During room sensor mounting, the address labels can be peeled off the devices
and stuck to a floor plan or similar to show the KNX IDs and the physical location in
one place.
After mounting/installation, the devices are detected after updating the ACS790
device list. The devices can be easily identified in the device list based on the
collected KNX IDs, and the physical addresses can be assigned as planned. As a
result, commissioning requires only very little effort.
7.2 Commissioning
Depending on the environment, both type and number of adjustable parameters
will vary. Prior to commissioning, all devices must be mounted as per the mounting
instructions [2] and connected to bus cabling. If available, pushbuttons and
external temp
eratu
re sensors must also be connected to the device. Bus cabling
must be tested.
Pushbutton actuation Meaning
Switch over to programming mode or acknowledge
display of a connection test.
Short (< 0.5 s)
No functions are executed when the programming
button is pressed longer (> 0.5 s to 2 s).
Medium-long (>2 s and <20 s) Special mode (connection test for Desigo TRA). This
manufacturer-specific function can lock the device for
programming mode for ca. 10 s. In this case, the LED
status indication briefly blinks (orange).
Long (> 20 s) Reset to factory settings.
LED indication Meaning
Orange Feedback on special mode.
Red Device is in programming mode.
All other indication types are irrelevant for KNX LTE-Mode.
Room sensor AQR257…, KNX LTE–Mode controllers, and operator units are
connected to power. Update first the ACS790 device list, then open.
Variant 1 (recommended)
1. Select a room sensor from the device list via the KNX ID
(KNX-IDs must be collected during mounting).
2. Double-click this line to open the "Address assignment" dialog.
or
ACS790 version
Recommendation: Keep
the adhesive address
labels
Commissioning
prerequisites
Pushbuttons
LED status indication
KNX LTE–Mode
commissioning