Data Sheet for Product

14
Siemens
A6V11893002_en--_c
Smart Infrastructure
2021-07-05
Functional data (temperature with QSM2162)
Range of use
-5…45 °C
Measuring range
0…50 °C/-35…35 °C
Measuring accuracy at DC 24 V in the range of
20…25 °C
15…35 °C
-3550 °C
±0.3 k (typical)
±0.6 k
±1 k
Time constant t
63
< 3.5 min in 2 m/s moved air
Output signal, linear (terminal X3)
DC 0...10 V or DC 0...5 V
0...50 °C/-35…35 °C, max. ±1 mA
4...20 mA 0...50 °C/-35…35 °C, max. 500 ohm
Functional data (humidity with QSM2162)
Range of use
5…95 % r.h. (non-condensing)
Measuring range
0…100 % r.h.
Measuring accuracy at 23 °C and DC 24 V
0…95 % r.h.
30…70 % r.h.
±5 % r.h.
±3 % r.h. (typical)
Time constant t
63
Approx. 20 s
Output signal, linear (terminal X2)
DC 0...10 V or DC 0...5 V
0...100 % r.h., max. ±1 mA
4...20 mA 0...100 % r.h., max. 500 ohm
Functional data
Max. air velocity V
max
10 m/sec
Ambient conditions and protection classification
Protection degree of housing
IP54 as per EN 60529 in built-in state
Protection class
III as per EN 60730-1
Environmental conditions
Transport
Climatic conditions
Temperature
Humidity
Mechanical conditions
Operation
Climatic conditions
Temperature (housing with electronics)
Humidity
Mechanical conditions
IEC 60721-3-2
Class 2K3
-25...70 °C
< 95 % r.h.
Class 2M2
IEC 60721-3-3
Class 3K5
-5...45 °C
5…95 % r.h. (non-condensing)
Class 3M2