s Program Library Karlsruhe S79220-A0977-A-10-7637 Product Information AS 488/TM Var. M02.02 Issue: November, 2001 Descriptors TELEPERM M , AS 488/TM , Software variant M , UPGRADE , UPDATE Summary The present Product Information relates to the System Software Package: Name Variant Issue Product no. (MLFB) AS 488/TM M 02.02 6DS2 410-0XX00-0XA0 6DS2 410-0XX00-0XB0 AS 488/TM upgrade / update M 02.02 01.
Product Information AS 488/TM 1 November, 2001 M02.02 Scope The product information for the system software M02.01/M01.07 remains valid. The following information represents a supplement.
Product Information AS 488/TM November, 2001 M02.02 1.1 Supplementary Documentation In addition to the tools required for startup of your AS 488/TM, the commissioning diskette contains a document file for the service terminal (within the directory ASBEDIEN or ASBEDIEN.NT): ASBEDI_E.doc User description for the Commissioning Terminal (IBS terminal) For further information by seperate ordering to C79000-G8076-C700 please ask your Siemens sales partner for a document diskette.
Product Information AS 488/TM November, 2001 M02.02 1.2 AS System File for PROGRAF AS+ Your commisioning diskette contains a directory PROGRAF after extracting. This contains the system file AS.SYS required for PROGRAF AS+. Copy the file AS.SYS into your PROGRAF PC into the directory drv:\PROGRAF\USER\ The system file of the AS 488/TM automation system is then known to PROGRAF AS+. Carry out your PROGRAF AS configuring in the usual manner. Note: From PROGRAF AS+ V3.
Product Information AS 488/TM 2 November, 2001 M02.02 Commissioning The Memory Card contains the entire system software for AS 488/TM. It responds with the version ID M02.02 . To perform an upgrade or update from diskette, an AS 488/TM memory card must be available. The upgrade procedure is performed offline with a PC or a programming device having a compatible MC interface (e.g. PG740).
Product Information AS 488/TM November, 2001 M02.02 2.1 Startup by Commissioning Terminal The extracted IBS tool diskette contains your local tool in the directory ASBEDIEN. Install this on your PC to be used for commissioning of the AS 488/TM according to the installation instructions in the document file ASBEDI_E.DOC in the directory ASBEDIEN, and connect your PC to the serial commissioning interface of your AS 488/TM via a serial interface. For operation under Windows 3.
Product Information AS 488/TM November, 2001 M02.02 2.2 Procedure for Upgrade to M02.02 with Programming Device PG740 Stop your AS running (e.g. with STO) and then switch the AS off before pulling the memory card! For the upgrade, insert the memory card into the MEM-CARD slot of the PG740. Now start the batch UPGRADE.BAT (if applicable, information on the memory card drive, default setting is E:) resp. the corresponding link. Syntax: UPGRADE or UPGRADE E: This batch file - creates a directory C:\UPGRADE.
Product Information AS 488/TM November, 2001 M02.02 2.2.1 Restoring a Memory Card This restore is necessary if the memory card is no longer bootable on an AS 488/TM (if it has been deleted with the SIMATIC Manager for example). The procedure corresponds to an upgrade (see chapter 2.2).
Product Information AS 488/TM November, 2001 M02.02 2.3 Procedure for Update M01.07 (resp. M01.06/05/04) to M01.08 2.3.1 Update by Commissioning Terminal You will find the files needed for an update on the UPGRADE/UPDATE diskette too. Please copy all files from the directory C:\UPGRADE\AS_SW.202 (without sub-directory M02.02) and from the directory C:\UPGRADE\UPDATE_M.108 to the directory ‘C:\ASBEDIEN’ on your Commissioning Terminal PC or into the current working directory (e.g.
Product Information AS 488/TM November, 2001 M02.02 To check the update procedure, start the new ASBEDIEN and select the AS status screen ( BT,STAT:@; ). In addition to the start-up message, the system version ( M01.08 ) is displayed. Note: If there is already a version M02.01 on the memory card, you can use the files from directory C:\UPGRADE\AS_SW.202\M02.02 instead of the files from C:\UPGRADE\Update_M.108 for the online update (additionally to the files from C:\UPGRADE\AS_SW.202).
Product Information AS 488/TM November, 2001 M02.02 2.4 Installation of the Reloadable DP Driver Blocks (DPAE, DPAA, DPBE, DPBA) In addition to the execution system and the standard blocks of the AS 488/TM, your memory card contains a so-called reloadable file with the optimized driver blocks for the PROFIBUS-DP I/O bus. These blocks are not present in the system data area of the AS, and are thus not activated automatically. You can load these blocks into your user memory and activate them.
Product Information AS 488/TM November, 2001 M02.02 2.5 Installation of the Reloadable IP262 Driver Blocks (RIP, KRIP) In addition to the execution system and the standard blocks of the AS 488/TM, your memory card contains a so-called reloadable file with the optimized driver blocks for the controller module IP262. These blocks are not present in the system data area of the AS, and are thus not activated automatically. You can load these blocks into your user memory and activate them.
Product Information AS 488/TM 3 November, 2001 M02.02 Removed Errors F: Function concerned A: Appearance M: Modification • F: ASBEDIEN: command LANW A: The transmission doesn't work. Afterwards also the other commands don't work (COPY_PC, COPY_TM, DIR_TM). M: Operating task corrected within the AS system software. • F: S5KS/S5KE A: When utilizing the maximum permissible message frame length of 128 bytes with TELEPERM I/O modules, the telegram is rejected (shorter and longer telegrams are working).
Product Information AS 488/TM 4 November, 2001 M02.02 Extended Functions 4.1 General Extensions F: Function concerned A: Appearance E: Extension • F: Central configuration via bus A: If the disconnection is not finished correctly, the AS continues transmitting picture data (S 38x is appearing as error message). If another AS is selected from the configuration AS via ANMS, pictures were shown from the last linked AS and the new linked AS alternately.
Product Information AS 488/TM November, 2001 M02.02 4.
Product Information AS 488/TM 5 November, 2001 M02.02 Extended Documentation 5.1 Restart of AS 488/TM with Interface Module TPM 478 With each restart of the AS 488/TM the interface module TPM 478 will be parameterized new. This happens with: Power on Boot by MRES key switch RSOF (by operation or key switch) Loading (LA,name; or LA:name;) Loading via bus (LAB or LABR) LOES. During this parameterization the SYST.WART configuration is passed to the TPM 478 module, and a restart of the TPM 478 is activated.
Product Information AS 488/TM 6 November, 2001 M02.02 Limited Operating Performance No safety-relevant software faults are currently known; the known faults are assigned to fault class 3 and lower. Caution: When working on initialization files (*.INI), tabs (09H) should not be used. Spaces (20H) should be used instead. Failure to comply could lead to interpretation errors.
Product Information AS 488/TM November, 2001 M02.02 Further information: The arithmetic accuracy of the AS 488/TM with floating-point numbers is higher than that of the AS 235. There may therefore be small deviations in the last digits of the mantissa in the case of calculated analog values or floating-point constants in TML. The CD coupling is not implemented in the AS 488/TM. Any attempt to register a CD coupling from OS or AS 235 will be rejected.