Data Sheet for Product

s Industry, Inc.
Building Technologies Division
Technical Data
AH Series: Wall-only Mount
UL Current Ratings (AMPs) Average
Current
Volume Levels Low Medium High
DC 16.033.0VDC 0.021 0.043 0.080
FW R 16.033.0VRMS 0.041 0.051 0.090
AH Series: Wall-only Mount
ULC Current Ratings (AMPs) Average
Current
Volume Levels Low Medium High
20.0 VDC
0.014
0.020
0.035
24.0 VDC
0.017
0.025
0.050
31.0 VDC
0.021
0.030
0.065
AH Series AH Series
Description
UL / ULC dBA Sound Output
Reverberant
[
Per UL464 @ 10 Ft.
]
Anechoic
[
Per ULC-S525-99
]
Volume
Levels
16VDC
24VDC
33VDC 20VDC
24VDC
31VDC
Continuous
Horn
Low
80
83
86
88
90
92
Medium
85
88
91
90
95
97
High
88
91
93
92
97
99
Code 3 Horn or
March Time**
Low
75
79
82
88
90
92
Medium
80 84 86 90 95 97
High
84
87
90
92
97
99
** Available in sync mode only
Note: These notification appliances are UL Listed as “Special Application”.
They are intended to be used only with Siemens notification appliances.
AS Weatherproof Series
UL / ULC Models and Ratings
Model*
Operating Voltage
(Special Application)
Per UL 1638, UL1971
and UL464 (VDC/VRMS)
Voltage Range
Per CAN/ ULC-S525-99 /
S526-02 (VDC/VRMS)
UL Rated Strobe Candela (cd)
ULC Rated
Light Output
(cd)
At 40°C,
per UL1638
UL1971
AS-75-R-WP 16.033.0 20.033.0 115 30 / 180 * 30
AS-75-CR-WP
16.033.0
~
115
30 / 180 *
~
AS-HMC-C-WP*
16.033.0
~
50 / 75
115 / 177
~
AS-HMC-WP*
16.033.0
~
65 / 90
135 / 185
~
* Available in red or white.
AS-MC and AS-HMC Series
UL Listed Ratings
Model*
Operating Voltage
(Special Application)
Per UL 1971
(VDC / VRMS)
Strobe
Candela
(cd)
AS-HMC 16.0 - 33.0 135 / 185
AS-MC 16.0 - 33.0 15/30/75/110
AS-MC-C 16.0 - 33.0 15/30/75/95
dBA Sound Output
Description Volume
Reverberant Per UL 464
16.0 VDC
24.0 VDC
33.0 VDC
Continuous
Ho
rn
Low 80 83 86
Medium
85
88
91
High
88
91
93
Code 3 Horn
(or March Time)**
Low
75
79
82
Medium
80
84
86
High
84
87
90
** Available only in sync mode.
Notes: 1. Strobe will produce 1 flash-per-second over the Input Voltage range.
2. This strobe/horn model meets the required light distribution patterns defined in UL 1971.
3. This model is
UL Listed for indoor use with a temperature range of
+
32ºF to
+
120ºF (0ºC to
+
49ºC)
and maximum humidity of 93% + 2% RH.
The effect of shipping and storage temperatures will not adversely affect the performance
of the appliance when it is stored in the original cartons, and is not subjected to either
misuse or improper handling of shipment.
ULC Directional Characteristics
-3 dBA: 48 degrees left, 41 degrees right
-6 dBA: 50 degrees left, 58 degrees right