Data Sheet for Product
AS / AH Series Notification Appliances
2578
s Industry, Inc.
Building Technologies Division
s
Data Sheet
Fire Safety Products
Notification Appliances
AS & AH –
Audible Horn | Strobe / Audible Horn Appliances
Application:
Indoor / Outdoor
Product Overview
– Fast installation with In / Out screw terminals using
#
12 to
#
18 AWG wires
– Synchronization can be done via the Siemens 50-point, 252-point and 504-point
fire alarm control panels (FACPs), as well as with:
FireFinder® XLS and MXL® FACPs
PAD-3 or PAD-4™ NAC Extenders with built-in sync protocol
Siemens Dual Sync (DSC) modules
– Selectable Continuous Horn or Temporal (Code 3)
– Wall mounts are available with field-selectable Candela settings: 15/30/75/110cd or 135/185cd
– Ceiling-mount models are available with field-selectable Candela settings:
15/30/75/95cd or 115/177cd (multi-Candela ceiling models)
– Three (3) field-selectable dBA settings of 90/95/99 dBA Anechoic in both tones
– Weatherproof wall-mount models are available with field-selectable Candela settings: 135/185cd
– Weatherproof ceiling-mount models are available with field-selectable Candela settings: 115/177cd
– UL Listed & ULC Listed;
FM (
#
3150) and CSFM Approved (
#
7125-0067:0247 –> Fire Alarm Devices For The Hearing Impaired)
–
ADA / NFPA / UFC / ANSI compliant
Specifications
– Notification appliances are Siemens Series ‘AS’ Audible Horn | Strobe appliances and
Series ‘AH’ Audible Horn appliances or approved equals
– Series ‘AS’ Audible Horn | Strobes are listed for UL Standard 1971
(Emergency Devices for the Hearing-Impaired for
Indoor Fire Protection Service)
– Series ‘AH’ Audible Horns are UL Listed under Standard 464 (Fire Protective Signaling)
– All inputs are compatible with standard reverse polarity supervision of circuit wiring by
the Siemens Fire Alarm Control Panel (FACP)
– The audible portion of each appliance has a minimum of three (3) field-selectable settings for dBA
Anechoic levels, as well as a choice of continuous or temporal (Code 3) audible outputs
– The strobe portion of each appliance produces a flash rate of one (1) flash-per-second over the
Regulated Input Voltage Range, and incorporate a Xenon flashtube enclosed in a rugged Lexan® lens
AS-MC-CW
AS-MC-R
AH-R
AH-W