Data Sheet for Product

AS / AH Series Notification Appliances
2578
s Industry, Inc.
Building Technologies Division
s
Data Sheet
Fire Safety Products
Notification Appliances
AS & AH –
Audible Horn | Strobe / Audible Horn Appliances
Application:
Indoor / Outdoor
Product Overview
Fast installation with In / Out screw terminals using
#
12 to
#
18 AWG wires
Synchronization can be done via the Siemens 50-point, 252-point and 504-point
fire alarm control panels (FACPs), as well as with:
FireFinde XLS and MXL® FACPs
PAD-3 or PAD-4™ NAC Extenders with built-in sync protocol
Siemens Dual Sync (DSC) modules
Selectable Continuous Horn or Temporal (Code 3)
Wall mounts are available with field-selectable Candela settings: 15/30/75/110cd or 135/185cd
Ceiling-mount models are available with field-selectable Candela settings:
15/30/75/95cd or 115/177cd (multi-Candela ceiling models)
Three (3) field-selectable dBA settings of 90/95/99 dBA Anechoic in both tones
Weatherproof wall-mount models are available with field-selectable Candela settings: 135/185cd
Weatherproof ceiling-mount models are available with field-selectable Candela settings: 115/177cd
UL Listed & ULC Listed;
FM (
#
3150) and CSFM Approved (
#
7125-0067:0247 > Fire Alarm Devices For The Hearing Impaired)
ADA / NFPA / UFC / ANSI compliant
Specifications
Notification appliances are Siemens Series AS’ Audible Horn | Strobe appliances and
Series AH’ Audible Horn appliances or approved equals
Series AS Audible Horn | Strobes are listed for UL Standard 1971
(Emergency Devices for the Hearing-Impaired for
Indoor Fire Protection Service)
Series AH’ Audible Horns are UL Listed under Standard 464 (Fire Protective Signaling)
All inputs are compatible with standard reverse polarity supervision of circuit wiring by
the Siemens Fire Alarm Control Panel (FACP)
The audible portion of each appliance has a minimum of three (3) field-selectable settings for dBA
Anechoic levels, as well as a choice of continuous or temporal (Code 3) audible outputs
The strobe portion of each appliance produces a flash rate of one (1) flash-per-second over the
Regulated Input Voltage Range, and incorporate a Xenon flashtube enclosed in a rugged Lexan® lens
AS-MC-CW
AS-MC-R
AH-R
AH-W