Data Sheet for Product

s Industry, Inc.
Building Technologies Division
Specifications (continued)
Series AS Horn | Strobe appliances are of low current design
Strobe intensity (where Multi-Candela appliances are specified) is easily
controlled by field-selectable settings, and is rated per
UL Standard 1971 for:
15/30/75/110cd
135/185cd
When synchronization is required, Series ‘AS’ horn | strobe appliances are compatible with the
Siemens 50-point, 252-point and 504-point fire alarm control panels (FACPs), as well as with:
FireFinde XLS and MXL® FACPs
PAD-3 or PAD-4™ NAC Extenders with built-in sync protocol
Siemens DSC modules
The strobes will not drift out of synchronization at any time during operation
The strobes will revert to a non-synchronized flash-rate, if the sync module or Power Supply
should fail to operate (i.e.
contacts remain closed)
The appliance is also designed so that the audible signal may be silenced while maintaining strobe
activation when used with Siemens synchronization
The Series ASHorn | Strobe and Series AHHorn appliances incorporate a Patented Universal
Mounting Plate that allow mounting to a single-gang, double-gang, 4-inch (10.2 cm.) square,
Siemens SHBBS-Series surface backbox
All notification appliances are listed for Special Applications:
Strobes are designed to flash at 1-flash-per-second minimum over theirRegulated Input Voltage Range
Note: NFPA-72 specifies a flash rate of 1-to-2 flashes per second, and ADA Guidelines specify a flash rate
of 1-to-3 flashes per second
All Candela ratings represent minimum-effective Strobe intensity, based on UL Standard 1971
Mounting Diagram
Mounting Options
(Shown In Inches)
(Shown In Inches)