4.3 Function module AZX61.1
Acting direction Sequence control
OFF
1)
Direct acting positioning signal Y or Z Sequence control not active
ON
1)
Reverse acting positioning signal Y or Z
Sequence control
(signal adaptation)
1)
Factory setting: All switches set to OFF
4.3.1 Sequence control (signal adaptation)
Sequence control
ON
1)
Sequence control (signal adaptation)
1)
Factory setting: All switches set to OFF
Nr.: 1 Setting sequence control
Rotary switches LO and UP are used to set the starting point or
working range of a sequence.
Position
"LO"
Starting point
Position
"UP"
Working range
0 0,3 V 0 9,4 V
1 1 V 1 3 V
2 2 V 2 4 V
3 3 V 3 5 V
4 4 V 4 6 V
5 5 V 5 7 V
6 6 V 6 8 V
7 7 V 7 9 V
8 8 V 8 10 V
9 9 V 9 12 V
A 10 V A 14 V
B 11 V B 16 V
C 12 V C 18 V
D 13 V D 20 V
E 14 V E 25 V
F 15 V F 30 V
Invalid HEX switches combinations
LO 0 1 2 3 4 5 6 7 8 9 A B C D E F
UP F F F F F F F F F F D D C C B
UP E E E E E E E D D C
UP F F E E D
UP F F E
UP F
Can only be used with voltage input.
Maximum input voltage is DC 30 V. If the configuration is invalid, the actuator
operates on DC 0…10 V.