OpenAir External Auxiliary Switch Installation Instructions

Document No. 129-420
Installation Instructions
December 13, 2004
Manual Override
NOTE: When EAS is installed, you can still access the
manual override capability as shown in Figure
11.
0
0
GEB
GBB/GIB
GCA
GMA
EA1185R1
Figure 11. Manual Override.
Auxiliary Switches
CAUTION:
There should be no load on the actuator
when setting the auxiliary switches.
Setting the Switches
With the actuator in the full-closed (0°) position, press in
and turn with a Phillips screwdriver to the desired
setting. Release pressure to set the switch.
The switch is now set.
~3.5
mm
max.
10N
EA1186R1
5
25
45
55
65
75
85
35
15
85
75
65
55
45
35
25
15
5
5
25
45
55
65
75
85
35
15
85
75
65
55
45
35
25
15
5
Figure 12. Press In, Turn to Adjust, Release to Set Switch.
A
B
S1 S1
S4 S4
S2 S3 S2 S3
S5 S6 S5 S6
(Q12)
(Q14)
(Q14)
(Q12)
(Q22)
(Q24)
(Q22)
(Q24)
(Q11)
(Q11)
(Q21)
(Q21)
A
B
5
5
85
2
20 30 70 90
0
10
EA1187R1
Figure 13. Example of Switches Set to 5° and 85°.
Wiring
WARNING:
Do not mix operations. Apply only line voltage
or only Class 2 voltages to the switching
outputs of both auxiliary switches A and B.
A
24Vac...250V/6(2)A
(Q12)
(Q14)
(Q24)
(Q22)
S2 S3 S5 S6
S1 S4
(Q11)
(Q21)
B
EA1189R1
Figure 14. Wiring Diagram.
Wiring Designation
Wire Code Color Switch - Function
S1 Gray/red A Input
S2 Gray/blue A – NC
S3 Gray/pink A – NO
S4 Black/red B Input
S5 Black/blue B – NC
S6 Black/pink B – NO
Page 4 of 5 Siemens Building Technologies, Inc.