User Manual

58
Siemens A6V11422293_en--_b
Smart Infrastructure 2020-07-01
Commissioning: Differential pressure control
Valve control mode and characteristic
For
Differential pressure control
, no settings are needed in section
Valve
for control
mode or characteristic.
Limitation for differential pressure setpoint
1 2 3 4
Select Commissioning [1]. Select Limitation [2]. Select Setpoint differential pressure [3] to
set the local setpoint for Differential pressure
control.
Use slider and +/- to set differential
pressure setpoint;
Or enter value manually.