Technical data
Operating voltage 2 x 12 V~ via bus cable from the basic unit
or via a separate transformer
Drive motor Stepper motor
Power consumption
- SQM45...
-
SQM48...
9...15 VA
26...34 VA
Angular adjustment Max. 90°
Mounting position Optional
Degree of protection To EN 60529, IP54, provided adequate
cable entries are used
Safety class
III according to DIN EN 60730 part 1 and
part 2-14
External overload fuse Max. 4 AT (slow) to DIN EN 60127-2/5
Cable entry SQM45... / SQM48...:
Insertable threaded cable glands for
2 x M16
Direction of rotation (when facing the shaft)
∂ Standard
∂ Reverse
Counterclockwise
Clockwise
Torques and holding torques Refer to «Type summary»
Running times Refer to «Type summary» (can be selected
on the basic unit)
Drive shaft Supplied as standard, not replaceable
Weight
∂ SQM45...
∂ SQM48...
Approx. 1 kg
Approx. 1.6 kg
Temperature of the mounting surface Max. 60 °C
Life cycle 250,000 start cycles (CLOSE OPEN
CLOSE) under load with the rated torque
in the entire rotation angle range.
2,000,000 control cycles under load with
75% of rated torque in rotation angle range
of 10°.
On time 50 %, max. 3 min. continuously
Electrical connections RAST3.5 terminals
(for details, refer to the basic unit)
Ferrules Matching the dia. of the stranded wire
Direction of rotation Can be selected on the basic unit
Reproducibility (typically in the show-room
condition)
° 0.2° (when used with the basic unit
LMV5...)