User Manual
4/13
Building Technologies CC1N7814en
02.02.2018
Mounting notes (cont´d)
To ensure degree of protection IP54, suitable M16 glands must be fitted in the
actuator’s M16 openings. The M16 glands used must feature cable strain relief. To
ensure degree of protection IP54 during the actuator’s entire service life, the bearing of
the drive shaft must be located such that it will not be directly exposed to water or dust.
Mounting plate SQM45...
Secure coupling piece to drive shaft
such that intermediate plastic
piece has an axial play of about
0.2 to 0.5 mm
Mounting plate VKF41...
Spacer
VKF41...
ASK33.4
Warning!
SQM45.xxxB9 / SQM48.xxxB9 must be installed at a sufficient distance from
magnetic fields (e.g. permanent magnets, transformers, electric motors, etc.).
With magnetic fields of ′1000 mT, a minimum distance of 10 cm must be
complied with. For stronger magnetic fields (>1...10 T), a minimum distance of 40
cm must be complied with.
IP54
Mounting example