6
1)
For push-in lugs and auxiliary switches see Accessories.
2)
Selection depends on the motor full load amps. HP ratings for reference
only.
3)
Code for abbreviations:
RH = assembly kit for reversing duty with standard rail mounting adapter in
size S0.
RS = assembly kit for reversing duty with 8US Fast Bus busbar mounting.
4)
With standard rail mounting or screw fixing, the 3RA29 13-2AA2 wiring kit
and link module are required for size S00.
5)
The RH/RS assembly kits also include 3RA29 11-1CA00 spacer for height
compensation on AC contactors size S0 with spring-type terminals.
3RA22 10 3RA22 20 3RA22 10 3RA22 20
Reversing duty
Rated control supply voltage 24 V DC
With spring-type connection
These starters can be assembled in the field without
tools by simply snapping the components together.
Follow the simple component selection system to form
a starter.
Auxiliary switches
1)
on the motor starter protector and
the contactor can be easily fitted due to the modular
system.
With the contactor S0, an integrated NO contact is
available for free use.
Combination Starter, UL508 Type F
All size S00 and S0 devices can be applied as Combina-
tion Starters with the addition of either of these line side
connectors: 3RV29 28-1H, 3RV29 25-5EB or
3RV29 28-1K.
Size UL Data FLA set-
ting range
inverse-
time
delayed
overload
release
Consisting of the following single devices Not available
pre-assembled
Weight
approx.
Single-phase
HP ratings
Three-phase
2)
HP ratings
SCCR
at
480 V
Motor
starter
protector
+ 2 contac-
tors
Standard rail
or screw
mounting
+ Link module
+ Assembly kit
(RH)
3)
8US Busbar
mounting
system
+ Link module
+ Assembly kit
(RS)
3)
Spring-type
terminals
115 V 230 V 200 V 230 V 460 V 575 V Order No.
kA A kg
Selection depends on motor full load amps
3RV20 3RT20 3RA 3RA
S00 -- -- -- -- -- -- 65 0.14…0.2 11-0BA20 15-2BB42 2911-2AA00
+ 2913-2AA2
4)
2911-2AA00
+ 2913-1DB2
5)
0.641
-- -- -- -- -- -- 65 0.18…0.25 11-0CA20 0.641
-- -- -- -- -- -- 65 0.22…0.32 11-0DA20 0.641
-- -- -- -- -- -- 65 0.28…0.4 11-0EA20 0.641
-- -- -- -- -- -- 65 0.35…0.5 11-0FA20 0.641
-- -- -- -- -- -- 65 0.45…0.63 11-0GA20 0.641
-- -- -- -- -- -- 65 0.55…0.8 11-0HA20 0.641
-- -- -- -- -- 1/2 65 0.7… 1 11-0JA20 0.641
-- -- -- -- 1/2 1/2 65 0.9… 1.25 11-0KA20 0.641
-- 1/10 -- -- 3/4 3/4 65 1.1… 1.6 11-1AA20 0.641
-- 1/8 -- -- 3/4 1 65 1.4… 2 11-1BA20 0.641
-- 1/6 1/2 1/2 1 1 1/2 65 1.8… 2.5 11-1CA20 0.641
1/10 1/4 1/2 3/4 1 1/2 2 65 2.2… 3.2 11-1DA20 0.641
1/8 1/3 3/4 3/4 2 3 65 2.8… 4 11-1EA20 0.641
1/6 1/2 1 1 3 3 65 3.5… 5 11-1FA20 0.641
1/4 1/2 1 1 1/2 3 5 65 4.5… 6.3 11-1GA20 0.641
1/3 1 2 2 5 5 65 5.5… 8 11-1HA20 16-2BB42 0.641
1/2 1 1/2 2 3 5 7 1/2 65 7… 10 11-1JA20 0.641
1/2 2 3 3 7 1/2 10 65 9… 12 11-1KA20 17-2BB42 0.641
1 2 3 5 10 -- 65 11… 16 11-4AA20 18-2BB42 0.641
S0 1/6 1/2 1 1 3 3 65 3.5… 5 11-1FA20 24-2BB40 2921-2AA00
+ 2923-1BB2
5)
2921-2AA00
+ 2923-1DB2
5)
0.925
1/4 1/2 1 1 1/2 3 5 65 4.5… 6.3 11-1GA20 0.925
1/3 1 2 2 5 5 65 5.5… 8 11-1HA20 0.925
1/2 1 1/2 2 3 5 7 1/2 65 7… 10 11-1JA20 0.925
1/2 2 3 3 7 1/2 10 65 9… 12.5 11-1KA20 0.925
1 2 3 5 10 -- 65 11… 16 21-4AA20 26-2BB40 0.925
1 1/2 3 5 5 10 -- 65 14… 20 21-4BA20 0.925
1 1/2 3 5 7 1/2 15 -- 50 17… 22 21-4CA20 27-2BB40 0.925
2 3 5 7 1/2 15 -- 50 20… 25 21-4DA20 0.925
2 5 7 1/2 10 20 -- 50 27… 32 21-4EA20 0.925
Screw fixing with 2 push-in lugs each per motor starter is possible with RH configured starters.