Input Parameters
Parameter Data
Type
Value Range Default Description
COM_RST BOOL FALSE
COMPLETE RESTART. The block has a
complete restart routine that is processed if the
input is set to "Complete restart".
MAN_ON BOOL TRUE MANUAL VALUE ON / Switch on manual
operation. If the input "switch on manual
operation" is set, the control loop has been
interrupted. A manipulated value is entered as
manual value.
PVPER_ON BOOL FALSE PROCESS VARIABLE PERIPHERY ON /
Actual value
Switch on the periphery. If the periphery is to
read in the actual value, input PV_PER has to
be wired to the periphery, and the input "Switch
on actual value periphery" has to be set.
P_SEL BOOL TRUE PROPORTIONAL ACTION ON / Switch on P-
component. In the PID algorithm, the PID
components can be switched on/off individually.
The P-component is switched on if the input
"Switch on P-component" is set.
I_SEL BOOL TRUE INTEGRAL ACTION ON / Switch on I-
component. In the PID algorithm, the PID
components can be switched on/off individually.
The I-component is switched on if the input
"Switch on I- component" is set.
INT_HOLD BOOL FALSE INTEGRAL ACTION HOLD / Freeze I-
component. The output of the integrator can be
frozen. To this end, the input "Freeze I-
component“ is set.
I_ITL_ON BOOL FALSE INITIALIZATION OF THE INTEGRAL ACTION /
Set I-component. The output of the integrator
can be set to the input I_ITL_VAL. To this end,
the input "Set I-component“ has to be set.
D_SEL BOOL FALSE DERIVATIVE ACTION ON / Switch on D-
component. In the PID algorithm, the PID
components can be switched on/off individually.
The D-component is switched on if the input
"Switch on D-component" is set.