5. Battery
Wiring as refer to figure 6.
Maximum battery circuit
current
Charging: 3.1A
Discharging:6A
Capacity Sealed Leaded
Acid,12VDC,12Ah×2
Expected battery standby
operational times
24 Hours and 5 Minutes alarm
Dimension(mm) 181×76×167(L×W×H)
Battery Maintenance
Check battery regularly, if the following things happen, eg.
function is not normal, housing is distorted, liquid releases,
the battery must be changed. If the battery is dirty, please
use towel with warm water to clean it. Do not use petrol, or
chemical liquid.
To be stored at -10℃ ~ +50℃ temperature and dry place.
To be stored at full chargeable status. To be charged before being used because of self discharge.
6. Power supply load calculation table
No
.
Type Description Quantity Quiescent
current(mA)
Max.
current(mA)
Total Quiescent
current(mA)
1.
BDS031A Addressable heat detector 0.8 1.0
2.
BDS051A Addressable smoke detector 0.8 1.0
3.
BDS121A Manual signaling box 0.8 1.0
4.
BCC8001A Main Board+CPU 90.0 130.0
5.
BDS132A Input Module 1.0 3.0
6.
BDS221A Output Module 1.0 3.0
7.
NAC 0 1500.0
8.
U-MCS Multicandela selectable strobe(red) 0 145.0
9.
U-MMT-MCS Multitone horn Strobe(red) 0 200.0
10.
DSC Dual sync control module 0 55.0
11.
P2475 SpectrAlert horn/strobe 0 245.0
12.
MDL Sync-Circuit module 0 12.0
Total System Current
- + - +
Power Supply
Bat- Bat+
Battery Battery
Figure 6
Battery and AC power connection diagram