6. Fire Alarm Event Handling
Status:
LCD will display fire event automatically as Fire alarm screen”.
The red fire alarm LED is on.
Acknowledge LED is flashing.
Alarm Silence LED is flashing.
The buzzer and NAC devices are sounding.
How to do:
1. Press “Acknowledgebutton to acknowledge the alarm :
If current user level is 1, login window will be popup automatically. After
inputting level 2/3 password, press OKto enter alarm window. All alarm
events are acknowledged at the same time:
Symbol “*“ will be changed to #” automatically
Buzzer is silent
Acknowledge LED will change from flashing to steady
If current user level is 2/3, all alarm events are acknowledged at the same
time.:
Symbol “*“ will be changed to #” automatically
Buzzer is silent
Acknowledge LED will change from flashing to steady
2. Press alarm silencebutton to stop NAC devices. These allow operator to
deactivate or reactivate the NAC devices. When NAC devices are silenced, the
silence LED is on.
3. Read fire location on the display window.
4. Go to the indicated fire location to check and handle.
5. If the fire is emergency, call ‘119” at once. If the fire is minor incident, press reset
to return to normal status.(password is required.)
Property display: select one fire information and pressOKand screen will display as
figure 4. After finishing checking, press “C” to return to the previous window.
One or more alarms happen:
One or more alarm locations
First alarm message is selected
Alarm message can be scrolled with / key
Notes:
“<RT-Alarm: 01>means there are 1 alarm event in total.
01” represents the number of alarms.
“#” represents the event is acknowledged and “*”represents the event is not
acknowledged.
Fire alarm screen
<RTAlarm:1> L1 A
* 1 Room 102 heat detector
L3 A
Addr 01.003.001
Te xt Room 102 Heat Detector
Type BDS031 Heat Point Dete
Status Fire