Installation guide

Mobility and Logistics, Traffic Solutions
Sopers Lane, Poole, Dorset, BH17 7ER
Security classification Unrestricted Page 62 of 84
Version 1 Status Issued
Last Editor Carl Rabe Date 11-Dec-2014
Document Name Stratos Outstation General and ICM Handbook Document No. 667/HB/52250/000
Copyright © Siemens plc 2014. All Rights Reserved. Mobility and Logistics is a division of Siemens Plc
I/O & PSU Card
LED State Description
SYS / RUN
System / Run
(Green)
Slow Flash Normal Operation.
Medium Flash Configuration or Firmware Download in progress.
Double Pulse Low power mode.
COMMS
Communications
(Green)
On Normal operation, GSPI messages being received
regularly.
Off No relevant GSPI messages received in the last
second (implies loss of communications), or low
power mode.
FLT – Fault
(Red)
Off Normal operation.
On Fault detected. Refer to Table 10 and Table 19 for
details of possible faults.
Double Pulse Firmware is in Error and low power mode.
Table 28 – PSU & I/O Board LED States
5.14 Testing, Validation and Site Acceptance
The installation should be tested in accordance to the relevant section for the feature(s)
used.
Run the system test scenario.
Site Acceptance Test (SAT) sheet (667/CI/31601/002) should be followed and completed
to ensure that the installation has been completed to a good standard, and that the
outstation is running properly.
The Relevant Setup Form (dependant on feature(s) used) should be completed and left in
the controller cabinet.
Eg. Stratos Outstation UTMC Commissioning Data 667/CI/52250/000