Specifications

Mobility and Logistics, Traffic Solutions
Sopers Lane, Poole, Dorset, BH17 7ER
Security classification Unrestricted Page 71 of 83
Version 2 Status Released
Last Editor Harry Smyth Date 09/12/2014
Document Name Configuration Control Document No. 667/CC/45950/000
Copyright © Mobility 2014. All Rights Reserved. Mobility is a division of Siemens Plc
4.12.2 Two Amp Ancillary Power Supply
On those occasions when additional -24 AC power is required, and a second HPU has not
been specified, an additional 2 Amp DC RMS power supply can be provided. This should be
positioned above the HPU on the left hand panel. Additional information on this exact
position may be sought from drawing 667/GA/33075/ETC.
With reference to the Figure 64, 64 and 65 the AC input for the ancillary power supply
should be obtained from the MCB on the master switch unit (Live connected to MCB SW1,
Neutral connected to Terminal N3). The step down transformer will be supplied with
conventional power supply leads, to allow this connection.
The AC output from the transformer is rectified and applied to a terminal block, as detailed in
the figues below. Orange coloured wire will be used to connect the DET COM + output from
the rectifier to the terminal block. Slate wire will be used to connect DET SUP -24V from the
rectifier to the terminal block. Please refer to 667/GA/33075/ETC for a detailed connection
scheme and earth arrangement.
Please Note! 2 Amp power supplies contain both transformer and associated rectifier.
When specifying multiple power supplies care should be taken to ensure that there is
sufficient space within the specified cabinet for the required items.
Please note! If it is anticipated that multiple 2 Amp power supplies will be required, to
service the configured load, AC input for the additional powers supplies should be
provided by configuring the ST950ELV controller with additional MCB.
Figure 64 Detector Power Figure 65 –Detector Power
Figure 66 – Detector Power
DET COM +
Orange
Output from Step
Down
transformer
DET COM +
Orange
Mains Power provided from
the Master Switch Unit
MCB
Live + VE
Neutral - VE
N3
SW1