Data Sheet for Product

Siemens Data Sheet 9822
Smart Infrastructure Building Products usa.siemens.com/fire
Marine Fire and Detection Control is an advanced Siemens fire-safety system
designed for use with Cerberus PRO 252-point (Model FC922) or 504-point
(ModelFC924) addressable FACPs for Marine-specific installs and other harsh-
environment applications.
The enclosure used in Marine applications is robust and weather-resistant. Its
durable design is customized for Marine installs, due to the conditions at-sea
the equipment will regularly encounter. In order to provide secure fastening,
each Model FH-2071-UM shipment includes a fully gasket-sealed outer door,
draw latches, as well as wire-braided, corrosion-resistant vibration isolators.
For all Marine installations that use Siemens XTRI-series devices, a specific
faceplate (Model USCG-XPLATE) is required, and must be ordered separately.
The faceplate helps diminish RFI exposure, and fits on the front of each XTRI
interface module.
Additionally, the system batteries (Model BP-62) are used to provide back-up
system power. Each battery, which is rated at 16AH, can withstand
temperatures as low as-40°F/°C and as high as+176°F (+80°C).
The equipment used in Marine applications generates and radiates radio-
frequency energy. If the equipment is not installed properly, and is attempted
to be used in ways that are different from the instructions found in the manual
(IOM: A6V10519176), this could subsequently result in interference with
radio communications.
With the exception of the inner door, the Marine enclosure (Model FH-2071-
UM) is shipped complete. A trained Siemens representative is required to wire
and assemble the Marine equipment at the site. Actual FACPs are delivered in
individual parts. Pre-installed components include one (1) EMI filter, as well as
one (1) system battery bracket.
The following components
must be ordered separately:
one (1) system operating
unit
one (1) 170W power
supply; electronic
components (according to
specified order)
two (2) 16AH batteries;
installation material,
instructions, and option
modules (as required).
See: Pages 4-6 for the
complete list of individual,
orderable parts.
Note: Cerberus PRO Marine Fire and Detection Equipment is UL 864 10th Edition
Listed; USCG Approved (per CFR, Title 46, Subpart 161.002/ 60/ 0). (Refer to Cerberus
PRO’s 252 / 504-point addressable panel datasheet, #9815, for more data.)
Cerberus® PRO
Marine Fire and Detection Equipment
Models FH-2071-UM I BP-62 I USCG-XPLATE
Architect & Engineer Specifications
Marine equipment is used with Cerberus
PRO 252-point (Model FC922) and 504- point
(Model FC924) addressable fire alarm control
panels (FACPs)
Robust design allows for protection of
equipment in harsh climates and
environments:
most parts used in Marine fire
applications have passed salt-spray mist
requirements for Exceptional Degree of
Protection , per USCG guidelines,
including Models OH921 | OP921| HI921
and Siemens H’ and ‘X’- series devices
Physical properties of Model FH-2071-UM
enclosures include:
fully gasket-sealed outer door
draw latches for secure closure
wire-braided, corrosion-resistant
vibration isolators
one (1) battery bracket which holds two
(2)16AH batteries
one (1) AC line EMI filter
Battery set (Model BP-62) provides back-up,
emergency power for Marine-only
installations
16AH Standby power @ 24VDC
with metal jacket, operable between -
40°F / °C to176°F (80°C)
comes with two (2) batteries per order
Model USCG-XPLATE is required for Marine
applications, in order to reduce radio-
frequency interference (RFI)
Ordered separately, each faceplate fits
over Model XTRI-series devices
UL 864 10th Edition Listed, ULC-S527 Listed
ABS Type Approval; Lloyd's Register Type
Approval
United States Coast Guard (USCG) Approved,
including Exceptional Degree of Protection
- CFR, Title 46, Subpart 161.002/ 60/ 0
Product Overview
Application Data
Model
FH2071-UM

Summary of content (6 pages)