User Manual
Siemens Building Technologies CM2N8892en / 02.2000
Landis & Staefa Division 1/4
8
892
VISONIK
®
Optimum Start/Stop Program BPS
Function sheet
The Optimum Start/Stop Program OSTP of the VISONIK BPS is used to optimally
control energy consumption of building zones. The OSTP aims at achieving the
longest possible temperature setback on heating and temperature increase on
cooling during the night, weekends, and holidays.
To achieve optimal energy control of a building, it is divided into zones as shown below
by two heating zones:
T
B
B
Start Stop
Start
Stop
T
T
T
Zone South
Zone North
Production
Offices
Ref
8892Z01E
Ref
A building zone may comprise one or several rooms. The building zone must fulfil the
following conditions:
– All rooms within a building zone are controlled by the same building services system.
– All rooms within a building zone have the same occupancy hours (B).
– Each building zone must have a designated reference room. This room's inside
temperature (T Ref) serves as the comfort temperature's actual value to control all
rooms belonging to this building zone.
Use
Building zones for
optimal control
Conditions for the
building zones