User Manual

CE1N1991en
2016-04-08
Building Technologies
1
991
Setpoint Adjusters, passive
BSG21…
Passive setpoint adjusters
· For controllers with a 0...1000 Ohm input
· For controllers with a LG-Ni 1000 input
· Choice of setting ranges, depending on the type of setpoint adjuster
Functions
The BSG21... setpoint adjusters are passive, infinitely adjustable signal transmitters.
They transmit the adjusted resistance value directly to the connected controller.
Type summary
There are 4 different types are available, the difference being the temperature setting
range and the resistance value:
BSG21.1 range 0 °C ... 50 °C (0...1000 Ω) setpoint adjuster (plus other scales)
BSG21.2 range 0 °C ... 50 °C (1000…1235 Ω) setpoint adjuster (LG-Ni 1000)
BSG21.3 range 10 °C ... 30 °C (1045…1138 Ω) setpoint adjuster (LG-Ni 1000)
BSG21.5 range -20 °C ...+20 °C ( 913…1091 Ω) setpoint adjuster (LG-Ni 1000)
range 20 °C ... 60 °C (1091…1285 Ω) setpoint adjuster (LG-Ni 1000)
range -3 K ... +3 K (1000…1175 Ω) setpoint adjuster (0K
1091
Ω)

Summary of content (4 pages)