Installation Instructions

Chapter 3 - Mounting
Cooling
27 | 82
Siemens Industry, Inc.
Smart Infrastructure
Siemens BT300 HVAC Drive
Installation Instructions
DPD01148
2019-05-29
Minimum Clearance in Inches (mm).
Type
A
1
B
1
C
D
FS4
0.78 (20 )
0.78 (20 )
3.93 (100)
1.96 (50)
FS5
0.78 (20 )
0.78 (20 )
4.72 (120)
2.36 (60)
FS6
0.78 (20 )
0.78 (20 )
6.29 (160)
3.14 (80)
FS7
0.78 (20 )
0.78 (20 )
9.84 (250)
3.93 (100)
FS8
0.78 (20 )
0.78 (20 )
11.8 (300)
5.90 (150)
FS9
0.78 (20 )
0.78 (20 )
13.8 (350)
7.87 (200)
1)
Minimum clearances A and B for drives with UL Type
12/IP54 enclosure is 0 in. (0 mm).
Type
Cooling Air Required in m
3
/h (ft
3
/h)
FS4
45 (1,589)
FS5
75 (2,647)
FS6
190 (6,710)
FS7
185 (6,533)
FS8
335 (11,830)
FS9
621 (21,930)
NOTE:
If several units are mounted above each other, the required free space equals C +
D (see the following figure).
The outlet air used for cooling by the lower unit must be directed away from the
air intake of the upper unit with a piece of metal plate mounted to the cabinet wall
between the drives as shown in the following figure.
When planning the air circulation inside cabinets, recirculation of the air must be
avoided.