Installation Instructions

Chapter 4 - Power Cabling
Cooling
29 | 82
Siemens Industry, Inc.
Smart Infrastructure
Siemens BT300 HVAC Drive
Installation Instructions
DPD01148
2019-05-29
Cable Type
EMC Levels
1
st
Environment
2nd Environment
Category C2
Category C3
Level C4
Line voltage cable
1
1
1
Motor cable
3*
2
2
Control cable
4
4
4
*360º grounding of the shield with cable glands in motor end needed for EMC
level C2.
1
=
Power cable intended for fixed installation and the specific line voltage.
Shielded cable not required. (MCMK or similar recommended).
2
=
Symmetrical power cable equipped with concentric protection wire and
intended for the specific line voltage. (MCMK or similar recommended).
See the following figure.
3
=
Symmetrical power cable equipped with compact low-impedance shield
and intended for the specific line voltage. [MCCMK, EMCMK or similar
recommended; Recommended cable transfer impedance (1 to 30 MHz)
max. 100mohm/m). See the following figure.
4
=
Screened cable equipped with compact low-impedance shield (JAMAK,
SAB/ÖZCuY-O or similar).