Installation Instructions

Chapter 4 - Power Cabling
Cable Installation
33 | 82
Siemens Industry, Inc.
Smart Infrastructure
Siemens BT300 HVAC Drive
Installation Instructions
DPD01148
2019-05-29
Distance Between
Cables, m (ft)
Shielded Cable, m
(ft)
1.0 (0.3)
≤ 164 (50)
3.2 (1.0)
≥ 656 (200)
1.
Strip the motor and line voltage (mains) cables as outlined in the following figure
and table.
Frame
A1
B1
C1
D1
C2
D2
E
FS4
0.59 (15)
1.38 (35)
0.39 (10)
0.78 (20)
0.27 (7)
1.38 (35)
Leave as
short as
possible
FS5
0.78 (20)
1.57 (40)
0.39 (10)
1.18 (30)
0.39 (10)
1.57 (40)
FS6
0.78 (20)
3.54 (90)
0.59 (15)
2.36 (60)
0.59 (15)
2.36 (60)
FS7
0.78 (20)
3.15 (80)
0.78 (20)
3.15 (80)
0.78 (20)
3.15 (80)
9019.emf
D1
B1
C1
A1
D2
C2
E
Earth conductor
MAINS MOT OR
Earth conductor