Installation Instructions
Chapter 4 - Power Cabling
Cable Installation
36 | 82
Siemens Industry, Inc.
Smart Infrastructure
Siemens BT300 HVAC Drive
Installation Instructions
DPD01148
2019-05-29
Figure 18: Cable Entry Plate and Cables.
7.
Connect the stripped cables (see Figure 18 [➙ 33] and Table [➙ 33]17) as
shown in Figure 25 [➙ 33].
• Expose the shield of all three cables in order to make a 360-degree
connection with the cable clamp (1).
• Connect the (phase) conductors of the supply and motor cables into their
respective terminals (2).
Form the rest of the cable shield of all three cables into “pigtails” and make a
grounding connection with a clamp as shown in Figure 25 [➙ 33] (3). Make the
pigtails just long enough to reach and be attached to the terminal - not longer.
Figure 19: Cable Connection.
U V W
R+ R-
9232.emf
L1L2L3 R+R- U V W
1
2
3
3
Supp
lycable
Brakecable
Mo
tor
cable
Brakeresistors
9230.emf