Installation Instructions

Chapter 4 - Power Cabling
Cable Installation
48 | 82
Siemens Industry, Inc.
Smart Infrastructure
Siemens BT300 HVAC Drive
Installation Instructions
DPD01148
2019-05-29
13.
Check the connection of the grounding cable to the motor and the drive
terminals marked with .
NOTICE
Two protective conductors are required according to standard EN 61800-5-1. For
more information, see the
Grounding and ground fault protection
section [ 10].
Connect the protective conductor using a cable shoe and an M8 screw (included
in the
Accessories bag
) on either of the screw connectors as advised in the
following figure.