Installation Instructions
Chapter 5 - Control Unit
I/O Cabling and Fieldbus Connection
56 | 82
Siemens Industry, Inc.
Smart Infrastructure
Siemens BT300 HVAC Drive
Installation Instructions
DPD01148
2019-05-29
NOTICE
When planning the cable runs, remember to keep the distance between the
Ethernet cable and the motor cable at a minimum of 11.8 in (30 cm).
Figure 44: Distance between cables, Left: IP 21, Right: IP54.
For more detailed information, see the user’s manual of the fieldbus you are using.
Prepare for use through RS-485
RS-485 Cable Data
Table 21: RS-485 Cable Specifications.
Connector
14 AWG (2.5 mm
2
)
Cable type
Multi-Conductor - Low Capacitance Computer Cable
for EIA RS-485 Applications 1-Pair 24 AWG,
polyethylene insulation, STP (Shielded Twisted
Pair), PVC jacket (Anixter #B9841 or similar)
Cable length
Depends on the used fieldbus. See respective bus
manual.
1. Strip about 0.6 in (15 mm) of the RS-485 cable (see the specification table in
this section) and cut off the gray cable shield. Do this for both bus cables.
2. Leave no more than 0.4 in (10 mm) of the cable outside the terminal block and
strip the cables at about 0.2 in (5 mm) to fit in the terminals. See the following
illustration.
9056.emf
Ethernet
cable