Installation Instructions
Chapter 6 - Commissioning
Running the Motor
66 | 82
Siemens Industry, Inc.
Smart Infrastructure
Siemens BT300 HVAC Drive
Installation Instructions
DPD01148
2019-05-29
• Check that the control cables are located as far as possible from the power
cables, see Chapter 4.2.
• Check that the shields of the shielded cables are connected to protective
ground marked with .
• Check the tightening torques of all terminals
• Check that the wires do not touch the electrical components of the drive.
• Check that the common inputs of digital input groups are connected to +24V or
ground of the I/O terminal or the external supply.
• Check the quality and quantity of cooling air (Chapter 3.2 and Table 13).
• Check the inside of the drive for condensation.
• Check that all Start/Stop switches connected to the I/O terminals are in
Stop-position.
• Run the Startup Wizard (see the
Siemens BT300 HVAC Drive Operator's
Manual (DPD01809).
Running the Motor
Motor Run Check List
WARNING
Before starting the motor, check that the motor is mounted properly and ensure
that the machine connected to the motor allows the motor to be started.
Avant de démarrer le moteur, verifies que le moteur est correctement installé,
et assurez-vous que le machine connecté au moteur permet à celui-ci d’être
démarré.
WARNING
Set the maximum motor speed (frequency) according to the motor and the
machine connected to it.
Régler la vitesse maximum du moteur (fréquence) en function du moteur et de la
machine à laquelle il est connecté.
WARNING
Before reversing the motor ensure that this can be done safely.
Avant d’inverser le moteur, vous assurer que cela peut être effectué en toute
sécurité.
WARNING
Ensure that the power correction capacitors are not connected to the motor cable.
Vous assurer que les condensateurs d’amélioration du facteur de puissance ne
sont pas connectés au câble du moteur.