Chapter 6 - Commissioning
Installation in an IT System
70 | 82
Siemens Industry, Inc.
Smart Infrastructure
Siemens BT300 HVAC Drive
Installation Instructions
DPD01148
2019-05-29
Figure 55: Location of the EMC-jumpers in Frame FS6.
2. Disconnect the RFI-filters from ground by removing the EMC-jumpers using
long-nose pliers or similar. See the following figures.