Installation Instructions
Chapter 6 - Commissioning
Installation in an IT System
71 | 82
Siemens Industry, Inc.
Smart Infrastructure
Siemens BT300 HVAC Drive
Installation Instructions
DPD01148
2019-05-29
Figure 56: Removing the Jumper, FS6 as Example.
Frames FS7 and FS8
Use the procedure in this section to modify the EMC protection of the drive of
frames FS7 and FS8 to EMC-level C4.
1. Remove the main cover of the drive and locate the jumper. FS8 only: Push
down the grounding arm. See the following figure.
Figure 57: Grounding Arm, FS8.
9239.emf
9060.emf