Chapter 6 - Commissioning
Maintenance
76 | 82
Siemens Industry, Inc.
Smart Infrastructure
Siemens BT300 HVAC Drive
Installation Instructions
DPD01148
2019-05-29
Maintenance Interval
Maintenance Action
Regularly and according to general
maintenance interval
Check tightening torques of terminals.
Check filters.
6 to 24 months (depending on
environment)
Check input and output terminals and control I/O
terminals.
Check operation of cooling fan.
Check for corrosion on terminals, bus-bars and other
surfaces.
Check door filters in cabinet installations.
24 months
Clean heat sink and cooling tunnel.
3 to 6 years
Change internal Type 12/IP54 fan.
6 to 10 years
Change main fan.