Installation Instructions

Chapter 7 - Technical Data
Technical Data
78 | 82
Siemens Industry, Inc.
Smart Infrastructure
Siemens BT300 HVAC Drive
Installation Instructions
DPD01148
2019-05-29
Specification
Description
Input Voltages and Power Ranges
(3-phase)
208 to 240 Vac (-10% to +10%):
1 hp to 125 hp (0.75 kW to 90 kW)
380 to 500 Vac (-10% to +10%):
1.5 hp to 250 hp (1.1 kW to 160 kW)
525 to 600 Vac (-10% to+10%):
3 hp to 200 hp (2.2 kW to 132 kW)
Input Frequency
45 to 66 Hz (50 to 60 Hz; -5% to +10%)
Output Voltage
0 to Input voltage
Output Frequency
0 to 320 Hz
Output Frequency Resolution
0.01 Hz
Efficiency
>97.5%
PWM (switching) frequency
FS4 to FS6 - 1.5 to 10 kHz
Default FS4: 6 kHz; FS5: 4 kHz; FS6 = 4 kHz
FS7 to FS9 - 1.5 to 6 kHz
Default FS7: 4 kHz; FS8: 3 kHz; FS9: 2kHz
Adjustable in .1 kHz increments
Automatic switching frequency derating in case of overheating
Short circuit withstand rating
100,000 AIC
Frequency Reference
Analog Input
Keypad
Resolution 0.01 to 0.1% (10 bit), accuracy ±1%
Resolution 0.01 Hz
Field weakening point
8 to 320 Hz
Acceleration time
0.1 to 3000.0 seconds
Deceleration time
0.1 to 3000.0 seconds
Ambient Operating Temperature
14°F (-10°C) (no frost) to 104°F (40°C)
up to 122°F (50°C) with derating
Relative Humidity
0 to 95% rh, non-condensing, non-corrosive
Air quality:
Chemical vapors
Mechanical particles
IEC 60068-2-60 (H
2
S [hydrogen sulfide] and SO
2
[sulfur dioxide]).
IEC 60721-3-3, unit in operation, class 3C2
IEC 60721-3-3, unit in operation, class 3S3.