Operating Instructions

Start-up Procedures
Startup Wizard (P1.19)
19
Siemens Industry, Inc. BT300 Bypass Operator's Manual DPD01391
Building Technologies 2017-09-28
Startup Wizard (P1.19)
The Startup Wizard prompts you for the essential information needed by the drive so
that it can start controlling the output as desired. Once power is connected to the
BT300 HVAC Drive, the Startup Wizard should run automatically. If it is not running, it
can be activated in the Quick Setup (M1) menu or by completing Restore Factory
Defaults (P6.5.1)
The following steps are required to successfully complete the Startup Wizard:
Step Parameter/Question Settings
1 Language Selections (P6.1) Select the icon for the language you want applied to the keypad. This
varies depending upon the language package installed.
2 Daylight Saving (P5.5.5) Select the Daylight Saving Rule
1 = Off
2 = EU
3 = US
4 = Russia
3 Time (P5.5.2) Specify the current time of day in the following format: hh:mm:ss where
h = hour, m = minute, s = seconds.
4 Year (P5.5.4) Specify the current year in the following format: yyyy where
yyyy = 4-digit year.
5 Date (P5.5.3) Specify the current date in the following format: dd.mm where
dd = 2-digit day, mm = 2-digit month.
6 Startup Wizard? Specify if the Startup Wizard should be activated: Yes, No
If the option Yes is selected for Startup Wizard (recommended), you will be prompted
for the following values:
Step Parameter/Question Settings
7 Fan or Pump
(Application Type)
Pump
Automatically sets the following:
Accel Time 1 (P1.13) = 30
Decel Time 1 (P1.14) = 30
Start Function (P3.2.4) = Ramping
Stop Function (P3.2.5) = Ramping
Fan
Automatically sets the following:
Accel Time 1 (P1.13) = 120
Decel Time 1 (P1.14) = 120
Start Function (P3.2.4) = Flying Start
Stop Function (P3.2.5) = Coast to Stop
8 Motor Nom Voltg (P3.1.1.1) Defines nominal motor voltage from motor nameplate data.
9 Motor Nom Freq (P3.1.1.2) Defines nominal motor frequency from motor nameplate data.
10 Motor Nom Speed (P3.1.1.3) Defines nominal motor speed from motor nameplate data.
11 Motor Nom Currnt (P3.1.1.4) Defines nominal motor current from motor nameplate data.
12 Motor Cos Phi (P3.1.1.5)
(Power Factor)
Defines nominal motor Cos Phi (power factor) from motor nameplate
data.