Operating Instructions

Troubleshooting
General Bypass
39
Siemens Industry, Inc. BT300 Bypass Operator's Manual DPD01391
Building Technologies 2017-09-28
Problem Description Possible Cause
Drive does not start on closing of the
run command.
The Siemens BT300 Bypass is not in Drive - Auto Mode.
Drive output contactor is not closed.
Remote contact is not closed. Replace with jumper to verify.
Run relay has failed.
Loose control wire connection.
The BT300 Drive Digital Input 1 is not programmed properly.
Diagnostic Test Points
The diagnostic board provides a centralized location for diagnostics troubleshooting.
The test points on this board make it easier to troubleshoot the bypass components.
Figure 9: Diagnostic Test Points.