SIEMENS Startup Procedure and Checklist Document No. 125-1006 Rev.
Startup Procedure and Checklist Document Number 125-1006 Rev. FA, June 18, 2019 Instructions Prerequisites Page 2 BT300 Variable Frequency Drives Complete all tabs of this workbook, when completed, e-mail to: ariane.roberson@siemens.com Note: It is recommended to save this file with the name being the serial number of the unit covered by this certification form For example: C131088747.xlsx.
Startup Procedure and Checklist Document Number 125-1006 Rev. FA, June 18, 2019 BT300 Variable Frequency Drives Record the site's unit identifier System Information Unit's Site Identifier: Record the motor nameplate data Motor Information Manufacturer: Model: Nominal Voltage: Nominal Frequency: Nominal Speed: Full Load Current (FLA): COSPhi / Power Factor: Service Factor: Nominal Power (HP): Record the drive information Drive Information Part Number: Serial Number: Software Version: (4.8.
Startup Procedure and Checklist Document Number 125-1006 Rev.
Startup Procedure and Checklist Document Number 125-1006 Rev. FA, June 18, 2019 BT300 Variable Frequency Drives Altitude Derating Calculator It is required to to derate the drive when altitudes are greater than 3280 feet. The following calculator can be used to determine if the drive size is proper. Enter the altitude - 3280 base value that does not require derating -3280 derate altitude -10.0000% derate percentage Enter drive amp rating 0.
Startup Procedure and Checklist Document Number 125-1006 Rev. FA, June 18, 2019 BT300 Variable Frequency Drives Preparing for BT300 VFD Startup In order to provide you with the most reliable drive available, and to avoid any extra costs related to loss or reduction of warranty coverage, a factory-certified specialist should complete the startup procedure. Please complete the checklist and maintain it in a secure location as technical service personnel may request information from this checklist.
Startup Procedure and Checklist Document Number 125-1006 Rev. FA, June 18, 2019 BT300 Variable Frequency Drives Startup Procedure for BT300 (Drive Only) Review the Preparing for BT300 VFD Start (tab 2) section in this document. Place a "X" in the check column when completed. Place a "n/a" if not used. Step Check Description Apply power to the drive. Make sure that all three input phases are present and that the input voltage is correct for the system being set up.
Startup Procedure and Checklist Document Number 125-1006 Rev. FA, June 18, 2019 BT300 Variable Frequency Drives Startup Procedure for Conventional Bypass Options (BTC…) Review the Preparing for BT300 VFD Start (tab 2) section in this document. Place a "X" in the check column when completed. Place a "n/a" if not used.
Startup Procedure and Checklist Document Number 125-1006 Rev. FA, June 18, 2019 21 22 23 BT300 Variable Frequency Drives The default display has been configured automatically to wait for 2 minutes of keypad inactivity and then switch to the multi-monitor display. If this is not acceptable, then refer to Timeout Time (5.7.1) and Default Page (5.7.2) for desired settings. Manually run the drive throughout its entire operation range while observing operation.
Startup Procedure and Checklist Document Number 125-1006 Rev. FA, June 18, 2019 BT300 Variable Frequency Drives Startup Procedure for Electronic Bypass Options (BTE…) Review the Preparing for BT300 VFD Start (tab 2) section in this document. Place a "X" in the check column when completed. Place a "n/a" if not used.
Startup Procedure and Checklist Document Number 125-1006 Rev. FA, June 18, 2019 17 18 BT300 Variable Frequency Drives Manually run the drive throughout its entire operation range while observing operation. If the drive trips on an over-current during acceleration, adjust the Accel time 1 (3.4.2). If the drive trips on an over-voltage during deceleration, adjust the Decel time 1 (3.4.3). If excessive vibration of the driven load is noted at specific input frequencies, use Prohibited Frequencies (3.
Startup Procedure and Checklist Document Number 125-1006 Rev. FA, June 18, 2019 Page 12 BT300 Variable Frequency Drives Siemens Industry, Inc.
Startup Procedure and Checklist Document Number 125-1006 Rev. FA, June 18, 2019 BT300 Variable Frequency Drives Place an "X" in the check column if there is a control wire terminaated at the associated block.
Startup Procedure and Checklist Document Number 125-1006 Rev. FA, June 18, 2019 BT300 Variable Frequency Drives Place an "X" in the check column if there is a control wire terminaated at the associated block.
Startup Procedure and Checklist Document Number 125-1006 Rev. FA, June 18, 2019 Name Example: RO1 Function Page 15 BT300 Variable Frequency Drives Menu 3.5.3.2.1 New Setting At Speed Siemens Industry, Inc.