Operating Instructions
Chapter 4 - Parameters and Menu Structure
Parameters (M3)
102 | 187
Siemens Industry, Inc.
Siemens BT300 HVAC Drive
DPD01809
Smart Infrastructure
2019-05-29
Figure 27: Feedforward Control.
Enable process supervision (P3.12.5.1)
Figure 28: Process Supervision.
Upper and lower limits around the reference are set. When the actual value goes above or below, a counter
starts counting up towards the Delay (P3.12.5.4). When the actual value is within the allowed area, the same
counter counts down instead. Whenever the counter is higher than the Delay, an alarm or fault (depending on
the selected response) is generated.
11108.emf
Regulating mode
Upper limit
P3.12.5.2)
Lower limit
(P3.12.5.3)
Actual value
Delay (P3.12.5.4)
Alarm or fault
Reference