Chapter 4 - Parameters and Menu Structure
Parameters (M3)
112 | 187
Siemens Industry, Inc.
Siemens BT300 HVAC Drive
DPD01809
Smart Infrastructure
2019-05-29
Selection
Selection Name
Description
0
Disabled
The priority/starting order of the motors is always 1-2-3-4-5 in normal
operation. It may have changed during its run if interlocks have been
removed and added again, but the priority/order is always restored after a
stop.
1
Enabled
The priority is changed at certain intervals to get an equal wear on all
motors. The intervals of the auto-change can be changedAutochInterval
(P3.14.5). You can also set a limit for how many motors are allowed to run
AutochMotorLimit (P3.14.7) as well as for the maximum frequency of the
regulating drive when the auto-change is done Autoch:FreqLim (P3.14.6).
If the auto-change interval Autoch Interval (P3.14.5) has expired, but the
frequency and motor limits are not fulfilled, the auto-change will be
postponed until all conditions are met (this is to avoid for example sudden
pressure drops while the system is performing an auto-change when there
is a high capacity demand at a pump station.
NOTE:
The warranty is void if the Fire Mode function is activated. Test Mode can be used
to test the Fire Mode function without voiding the warranty.