Operating Instructions

Chapter 4 - Parameters and Menu Structure
Parameters (M3)
113 | 187
Siemens Industry, Inc.
Siemens BT300 HVAC Drive
DPD01809
Smart Infrastructure
2019-05-29
Structure
Parameter
Unit
Min
Max
Default
ID
Description
P3.16.1
FireMode Passwd
0
9999
0
1599
Defines use of the Fire Mode.
Fire Mode is enabled when set
to a value of 1001. A test mode
can be entered by setting to a
value of 1234 previous to the
next activation as defined by
FireMode Activ.Open
(P3.16.2) or FireMode
Activ.Close (P3.16.3).
P3.16.2
FireMode Activ.Open
DigIN Slot0.2
1596
Defines location of fire mode
activation on contact opening.
Open Contact = Fire Mode
Active
Contact Closure = No Action
Also see Menu Structure
P3.5.1.39.
P3.16.3
FireMode Activ.Close
DigIN Slot0.1
1597
Defines location of Fire Mode
activation on contact closing.
Open Contact = No Action
Contact Closure = Fire Mode
Active
Also see Menu Structure
P3.5.1.40.
P3.16.4
FireMode Freq
Hz
0
Parameter
P1.9 or P3.3.2
0
1598
Defines the frequency setpoint
to be followed when fire mode
is activated as defined by
FireMode Active.Open
(P3.16.2) or FireMode
Activ.Close (P3.16.3) when
FireMode FreqSource
(P3.16.5) is defined as Fire
Mode Frequency.