Operating Instructions

Chapter 4 - Parameters and Menu Structure
Parameters (M3)
114 | 187
Siemens Industry, Inc.
Siemens BT300 HVAC Drive
DPD01809
Smart Infrastructure
2019-05-29
Structure
Parameter
Unit
Min
Max
Default
ID
Description
P3.16.5
FireMode
FreqSource
FireMode Freq
Motor Pot Ref
FireMode Freq
1617
Selection of the frequency
reference source to be
followed when fire mode has
be activated as defined by
FireMode Activ.Open
(P3.16.2) or FireMode
Activ.Close (P3.16.3).
Possible settings:
0 = Fire Mode Frequency (as
defined by FireMode Freq
(P3.16.4))
1 = Preset Speeds
2 = Keypad
3 = Fieldbus
4 = AI1
5 = AI2
6 = AI1 + AI2
7 = PID1
8 = Motor Potentiometer
P3.16.6
FireMode Reverse
DigIN Slot0.1
1618
Defines location of the reverse
command when Fire Mode is
active as defined by FireMode
Activ.Open (P3.16.2) or
FireMode Activ.Close
(P3.16.3).
Open Contact = Forward
Contact Closure = Reverse
NOTE: This function has no
effect in normal mode of
operation.
Also see Menu Structure
P3.5.1.4.
M3.16.7
FireMode Status
Disabled
Test Mode
Disabled
1597
Displays the status of the Fire
Mode as follows:
0 = Disabled
1 = Enabled
2 = Activated (Enabled and DI
active)
3 = Test Mode
M3.16.8
FireMode Counter
0
4294967295
1679
Displays the number of times
the Fire Mode has been
activated.
NOTE: This counter cannot be
reset.