Application Settings (M3.17)
The Applications Settings contain specific application information and are presented in the following table:
Table 72: Application Settings.Information.
Structure
Parameter
Unit
Min
Max
Default
ID
Description
P3.17.1
Password
0
65000
0
Location for entering a password
to the unit that will grant access
to development parameters.
P3.17.2
kW/HP Selection
kW
HP
HP
1198
Defines the selection of the unit’s
power type parameters.
Selectable for kilowatt or horse
power.
P3.17.3
°C/°F Selection
ºC
ºF
ºF
1197
Defines the selection of the unit’s
temperature type parameters.
Selectable for Celsius or
Fahrenheit.
P3.17.4
ByPass
Disabled
Electronic
Disabled
1809
Defines the bypass option
connected to the drive.
NOTE: To set the proper value for
this parameter, it is not
recommended to change this
parameter. This parameter is set
during the run of the Bypass
Wizard (P1.21)
Possible settings are as follows:
0 = Disabled
1 = Conventional
2 = Electronic
NOTE: The setting of Disabled
should also be used with all SED2
Migration Bypass Kits.
Bypass (M3.18)
The Bypass settings can only be accessed if Bypass (P3.17.4) is set to Electronic. The best way to set this is
by executing the Bypass Wizard (P1.21). The Bypass settings contain specific information about the
Electronic Bypass configuration.
The bypass settings are presented in the following table: