Operating Instructions

Chapter 4 - Parameters and Menu Structure
I/O and Hardware (M5)
125 | 187
Siemens Industry, Inc.
Siemens BT300 HVAC Drive
DPD01809
Smart Infrastructure
2019-05-29
Structure
Parameter
Min.
Max.
Default
ID
Description
P5.8.1.1
Protocol
No Protocol
Modbus RTU
No Protocol
2208
Defines the RS-485 base fieldbus protocol to
be used:
0 = No Protocol
1 = N2
2 = BACnet MS/TP
3 = P14 = Modbus RTU
NOTE: A new menu will be accessible at
M5.8.3 depending upon the protocol selected.
Configuration for protocol communications
will be within that menu.
NOTE: This selection enables monitoring
only. If control (start/stop and speed
reference) is to be from fieldbus, then Ctrl.
Place Auto (P3.3.1) must be set to
FieldbusCTRL.
Menu
Parameter
ID
Unit
Mn.
Max.
Default
Description
P5.8.3.1.1
Device Address
2350
1
255
1
Defines the unique slave address to be
used by the drive on the N2 network.
P5.8.3.1.2
Communications Timeout
2351
s
0
255
10
Defines the amount of time in which a
packet is not received before a
communications timeout is
faulted/alarmed.