I/O and Hardware (M5)
126 | 187
Siemens Industry, Inc.
Siemens BT300 HVAC Drive
DPD01809
Smart Infrastructure
2019-05-29
Menu
Parameter
ID
Min
Max
Description
M5.8.3.2.1
Fieldbus Protocol Status
2399
Initializing
Faulted
Displays the current protocol status as follows:
0 = Initializing
1 = Stopped
2 = Operational
3 = Faulted
M5.8.3.2.2
Communication Status
2400
0.0
99.999
Displays the number of bad frames and good
messages in the following format:
xx.yyy where xx indicates the bad frames and yyy
indicates the good messages.
M5.8.3.2.3
Invalid Data
2041
Active if one or more of the fields in a fieldbus
packet contains a value that is out of the
expected range.
M5.8.3.2.4
Invalid Commands
2402
Displays the number of commands that are not
appropriate for the field or record.
M5.8.3.2.5
Command NACK
2403
Displays the number of negative
acknowledgments due to problems with the
device, so the command was ignored.
M5.8.3.2.6
Control Word
2402
Displays the control word in a bit coded format
as follows:
B0 = Start/Stop
B2 = Fault Reset
M5.8.3.2.7
Status Word
2405
Displays the status word in a bit coded format as
follows: