Chapter 4 - Parameters and Menu Structure
I/O and Hardware (M5)
130 | 187
Siemens Industry, Inc.
Siemens BT300 HVAC Drive
DPD01809
Smart Infrastructure
2019-05-29
Menu
Parameter
ID
Unit
Min
Max
Default
Description
P5.8.3.1.1
Baud Rate
2392
bps
9600
76800
9600
on the network as follows:
1 = 9600
2 = 19200
3 = 38400
4 = 76800
P5.8.3.1.2
Autobauding
2330
Disabled
Enabled
Disabled
Defines if autobauding can be used to
configure the Baud Rate (P5.8.3.1.1).
P5.8.3.1.3
MAC Address
2331
1
127
1
Defines the unique device address for the
RS-485 network.
P5.8.3.1.4
Instance Number
2332
0
4194303
0
Defines the unique device address for the
IP network if a IP-MS/TP router is used.
P5.8.3.1.5
Communications Timeout
2333
s
0
65535
10
Defines the amount of time in which a
packet is not received before a
communications timeout is
faulted/alarmed.