Operating Instructions
Chapter 4 - Parameters and Menu Structure
I/O and Hardware (M5)
132 | 187
Siemens Industry, Inc.
Siemens BT300 HVAC Drive
DPD01809
Smart Infrastructure
2019-05-29
Table 97: BACnet Analog Inputs.
Instance ID
Object Name
Description
Units
PV Access
Menu
AI_0
ANALOG IN 1
This is the value of Analog Input 1
PCT
R
M2.2.13
AI_1
ANALOG IN 2
This is the value of Analog Input 2
PCT
R
M2.2.14
Binary Inputs (BI)
The binary inputs support the following BACnet properties:
● Active Text
● Event State
● Inactive Text
● Object Identifier
● Object Name
● Object Type
● Out of Service
● Present Value
● Status Flags
Table 98: BACnet Binary Inputs.
Instance ID
Object Name
Description
Active/Inactive Text
PV Access
Menu
BI_0
DI1 STATUS
Status of digital input 1 signal.
ON/OFF
R
M5.1.1
BI_1
DI2 STATUS
Status of digital input 2 signal.
ON/OFF
R
M5.1.2
BI_2
DI3 STATUS
Status of digital input 3 signal.
ON/OFF
R
M5.1.3
BI_3
DI4 STATUS
Status of digital input 4 signal.
ON/OFF
R
M5.1.4
BI_4
DI5 STATUS
Status of digital input 5 signal.
ON/OFF
R
M5.1.5
BI_5
DI6 STATUS
Status of digital input 6 signal.
ON/OFF
R
M5.1.6
Analog Outputs (AO)
The analog outputs support the following BACnet properties:
● Event State
● Object Identifier
● Object Name
● Object Type
● Out of Service
● Present Value
● Priority Array
● Relinquish Default
● Status Flags
● Units
Table 99: BACnet Analog Outputs.
Instance ID
Object Name
Description
Units
PV Access
Menu
AO_0
ANALOG OUT 1
Analog output command, if
configured.
PCT
C
M2.2.15