Operating Instructions
Chapter 4 - Parameters and Menu Structure
I/O and Hardware (M5)
133 | 187
Siemens Industry, Inc.
Siemens BT300 HVAC Drive
DPD01809
Smart Infrastructure
2019-05-29
Binary Outputs (BO)
The binary outputs support the following BACnet properties:
● Active Text
● Event State
● Inactive Text
● Object Identifier
● Object Name
● Object Type
● Out of Service
● Present Value
● Priority Array
● Relinquish Default
● Status Flags
Table 100: BACnet Binary Outputs.
Instance ID
Object Name
Description
Active/Inactive
Text
PV Access
Menu
BO_0
RO1 CMD
This object is the command of
the state for Relay Output 1
ON/OFF
C
FB ControlWord B13
BO_1
RO2 CMD
This object is the command of
the state for Relay Output 2
ON /OFF
C
FB ControlWord B14
BO_2
RO3 CMD
This object is the command of
the state for Relay Output 3
ON /OFF
C
FB ControlWord B15
BO_3
RUN ENABLE
Run Enable
ENABLE /
DISABL
C
BO_4
CMD RUN
STOP
Run Stop Command
RUN / STOP
C
FB ControlWord B0
BO_5
CMD FWD
REV
Forward Reverse Command
REVRSE /
FORWRD
C
FB ControlWord B1
Analog Values (AV)
The analog value support the following BACnet properties:
● Event State
● Object Identifier
● Object Name
● Object Type
● Out of Service
● Present Value
● Priority Array*
● Relinquish Default*
● Status Flags
● Units
* For commandable values only.