Operating Instructions

Chapter 4 - Parameters and Menu Structure
I/O and Hardware (M5)
135 | 187
Siemens Industry, Inc.
Siemens BT300 HVAC Drive
DPD01809
Smart Infrastructure
2019-05-29
Instance ID
Object Name
Description
Units
PV Access
Menu
AV_37
FBCTRLWORDHI
Fixed control word last 16 bits
C
M2.8.1
AV_38
FBSTATWORDLO
Fixed status word first 16 bits
R
M2.8.11
AV_39
FBSTATWORDHI
Fixed status word last 16 bits
R
M2.8.11
AV_40
MIN FREQ
Minimum Frequency
Hz
W
P3.3.1
AV_41
MAX FREQ
Maximum Frequency
Hz
W
P3.3.2
AV_42
ACCEL TIME
Acceleration Time (1)
s
W
P3.4.2
AV_43
DECEL TIME
Deceleration Time (1)
s
W
P3.4.3
AV_44
CURRENT LMT
Current Limit
A
W
P3.1.1.7
AV_45
MTRNOM CRRNT
Motor Nominal Current
A
W
P3.1.1.4
AV_46
MTRNOM POWER
Motor Nominal Power
HP
W
P3.1.1.6
AV_47
MTRNOM SPEED
Motor Nominal Speed
rpm
W
P3.1.1.3
AV_48
MTRNOM VLTG
Motor Nominal Voltage
V
W
P3.1.1.1
AV_49
MTRNOM FREQ
Motor Nominal Frequency
Hz
W
P3.1.1.2
AV_50
MOTOR COSPHI
Motor COSPHI
W
P3.1.1.5
AV_51
BYPASS
Bypass Type
R
P3.17.4
AV_52
BYP SAFESTAT
Bypass Safety Status
R
AV_53
BYP RUN TIME
Bypass Run Time
R
AV_54
PID1 GAIN
%
R
P3.12.1.1
AV_55
PID1 I TIME
s
R
P3.12.1.2
AV_56
PID1 D TIME
s
R
P3.12.1.3
AV_57
PID1 STATUS
R
M2.4.5
AV_58
PID1 STPT
R
M2.4.1
AV_59
PID1 FDBK
R
M2.4.2
AV_60
PID1 OUTPUT
R
M2.4.4
AV_61
PID2 GAIN
R
P3.13.1.3
AV_62
PID2 I TIME
s
R
P3.13.1.4
AV_63
PID2 D TIME
s
R
P3.13.1.5
AV_64
PID2 STATUS
R
M2.5.5
AV_65
PID2 STPT
R
M2.5.1
AV_66
PID2 FDBK
R
M2.5.2
AV_67
PID2 OUTPUT
PCT
R
M2.5.4
AV_68
ANY PARAM
ID number that is use in AV71
W
AV_69
ANY VALUE
Value of ID defined by AV70
W